Pre-Start Checkout

Unit Voltage Phasing

It is important that proper rotation of the compressors
be established before the unit is started. Proper motor
rotation requires confirmation of the electrical phase
FWD
sequence of the power supply. The motor is internally
Power supply
Capacities
connected for clockwise rotation with the incoming
Cooling capacity on water (1)
power supply phases A-B-C.
Heating capacity on water (2)
Fan motor
When rotation is clockwise, the phase sequence is
Fan power input (3)
Current amps (3)
usually called "ABC" , when counterclockwise "CBA" This
Start-up amps
direction may be reversed by interchanging any two of
Air flow
the line wires.
minimum
nominal
maximum
1. Stop the unit from TD7/UC800.
Main coil
2. Open the electrical disconnect or circuit protection
Water entering/leaving connections
switch that provides line power to the line power
Electric heater (accessory for blower only)
terminal block(s) in the starter panel (or to the unit
Electric power supply
mounted disconnect).
Heating capacity
3. Connect the phase-sequence indicator leads to the
Hot water coil (accessory for blower only)
Heating capacity (4)
line power terminal bloc (L1, L2, L3).
G2 filter (filter box accessory)
4. Turn power on by closing the unit supply-power
Quantity
fused-disconnect switch.
Dimensions ( LxWxth)
5. Read the phase sequence on the indicator. The ABC
G4 filter (filter box accessory)
Quantity
LED of the phase indicator will glow.
Dimensions ( LxWxth)
Condensate pump (accessory)
Water flow - lift height
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
Sound pressure level (5)
Sound power level (5)
Unit dimensions
Width x Depth
Height
Shipped unit dimensions
Width x Depth
Height
Weight
Colour
Recommended fuse size
Unit alone (aM/gI)
Unit with electric heater (gI)
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Heat exchanger operating limits:
FWD:
*water temperature: max 100° C
*absolute service pressure: min 1 bar/max 11 bars
Accessories - Hot water coil:
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
4
36
Technical Data
WARNING! It is imperative that L1, L2, and L3 in the
starter be connected in the A-BC phase sequence to
prevent equipment damage due to reverse rotation.
WARNING! To prevent injury or death due to
08
electrocution, take extreme care when performing
(V/Ph/Hz)
service procedures with electrical power energized.
(kW)
5,2
(kW)
6,3
CAUTION! Do not interchange any load leads that are
(type)
(kW)
0,23
from the unit contactors or the motor terminals. Doing
(A)
1,1
so may damage the equipment.
(A)
3,2

Water System Flow Rates

(m
/h)
490
3
(m
/h)
820
3
Establish a balanced chilled-water flow through the
(m
/h)
980
3
evaporator. The flow rates should be between the
(type)
minimum and maximum values given on the pressure
(Dia)
3/4"
drop curves.
(V/Ph/Hz)
230/1/50

Water System Pressure Drop

(kW)
2/4
Measure the water-pressure drop through the evaporator
(kW)
6,3
on the field installed pressure taps on the system water
2
piping. Use the same gauge for each measurement. Do
(mm)
386x221x8
not include valves, strainers, or fittings in the pressure
drop readings.
-
(mm)
-
(type)
(l/h - mm)
(dB(A))
36/40/43
(dB(A))
46/50/53
(mm)
890 x 600
(mm)
250
(mm)
933 x 644
(mm)
260
(kg)
32
(A)
8/16
(A)
16 (2kW),25 (4kW)
12
20
230/1/50
8,3
15
11,9
18,9
2 x direct drive centrifugal
0,46
0,65
2,2
3,1
5,5
9,3
980
1400
1650
2300
1970
2600
ISO R7 rotating female
3/4"
1 1/2"
230/1/50 or 400/3/50
400/3/50
8
10
12
17,4
2
2
486x271x8
586x321x8
2
2
486x264x48
586x314x48
Centrifugal
24 - 500
38/41/44
46/50/53
48/51/54
56/60/63
1090 x 710
1290 x 820
300
350
1133 x 754
1333 x 864
310
360
46
61
galvanised steel
8/16
8/16
40 (230V),3*16 (400V)
3*20
30
45
18,8
30,1
20,9
38,2
1,04
1,51
4,7
5,5
14,1
16,5
1800
2700
3000
4500
3600
5400
1 1/2"
1 1/2"
400/3/50
400/3/50
12
12
22,4
34,5
2
2
586*421*8
586*621*8
2
2
586*414*48
586*614*48
47/52/57
47/52/58
57/62/67
57/62/68
1290 x 970
1290 x 1090
450
650
1333 x 1008
1333*1133
460
660
76
118
8/25
8/25
3*25
3*25
UNT-PRC002-GB
RLC-SVX023A