54 Electrical installation
Connecting the control cables – ACS880-01 frames R1 and R2
1. Strip the cable ends and cut to suitable length (note the extra length of the
grounding conductors).
2. Ground the outer shields of all control cables 360 degrees at the cabinet entry.
3. Secure the cables mechanically at the clamps.
4. Ground the pair-cable shields to the clamps. Leave the other end of the shields
unconnected or ground them indirectly via a high-frequency capacitor with a few
nanofarads, eg, 3.3 nF / 630 V.
5. Connect the conductors to the appropriate terminals of the control board (see
section Default I/O connections in the hardware manual).
6. Wire the optional modules if included in the delivery.
5
4
5
0.5 N·m
1.5 N·m