Meter Settings

5.2 Setting the Alarm

About the alarm
The alarm function gives the user the possibility to set an alarm that will trigger
when a defined limit is reached by the measured value. See table for more infor-
mation.
Choice in menu
Alarm power
Alarm voltage Phase 1 V
Alarm voltage Phase 2 V
Alarm voltage Phase 3 V
Alarm current Phase 1 A
Alarm current Phase 2 A
Alarm current Phase 3 A
Alarm power factor
If the value is set above the max range, the meter will automatically set the value
to the max value allowed by the range.
Example: Alarm current is set to 100.0 A by the user, but the max value is 40.0
A, so the meter will use the max value, in this case 40.0 A.
If an alarm has been set, the output state will indicate if the alarm is triggered (AL
On) or not (AL OFF). The magnitude of the set alarm is also displayed in the
output state.
Set alarm
To set an alarm, perform the following steps when located in the view menu.
Step
1
2
3
4
C13
User Manual
Unit
W
-
Action
Use the long press to get to the set menu
Use the long press to get to the selection of
function menu
Toggle through the menu to choose what mag-
nitude to set. Choose one of the following:
Alarm power (W), Alarm voltage (V), Alarm
current (A) and Alarm factor (no magnitude).
Set the alarm value that the measured value
must pass in order for the alarm to trigger
(Alarm level on).
24
Output on display

W

V

V

V

A

A

A

Comment
-
-
Use the long press to choose.
Use the short press to change
the value of the digit, and the
long press to step through the
different digits.
Range
0–99999 W
0–299 V
0–299 V
0–299 V
0–40.00 A
0–40.00 A
0–40.00 A
0–0.999
2CMC486004M0201
Revision: A