Summary of Contents for Generac Power Systems PM-DCP
Page 1
PM-DCP 20-light Remote Annunciator O w n e r ’s M a n u a l GEN. BATTERY HIGH OVER OVER GEN. SYSTEM COMMS. RUN. CHARGER BATTERY BATTERY SENSOR CRANK SPEED POWER READY FAILURE VOLTAGE VOLTAGE LOSS PRE - ALARMS...
20-light Remote Annunciator Detailed Specifications ..........2 System Ready..............5 Environmental Specifications ........2 Communication OK ............6 Power Supply Requirements..........2 Audible Annunciator ............6 Communication With Generator Control System ..2 Test Switch ..............6 Interface With Other Equipment ........2 Re-Arm Horn Switch ............6 Agency Compliance ............2 Reset Switch ..............6 Transportation and Storage ..........2 Relay Output ..............6...
20-light Remote Annunciator The Remote Annunciator panels (Models 004996-0, and PACKAGING AND MOUNTING 004998-0) are mounted using any combination of the Enclosure type Sheet metal box. mounting holes in the back panel of the box itself. Base panel Generac part #0A6985/0A7437 Surface Mount Dimensions Front panel Generac part #0A6988/0A7443...
20-light Remote Annunciator An annunciator connected to a system controller would The ‘Re-Arm Horn' switch can be used to turn off and be a slave. re-arm the horn, or the alarms can be fully acknowl- edged using the ‘Reset' switch. Annunciator Connected to System Controller The ‘Reset' switch will turn off and re-arm the horn, and any flashing lights will switch to the ON state until the...
20-light Remote Annunciator GENERATOR POWER BATTERY CHARGER AC FAILURE This light indicates different things depending on the This light annunciates upon loss of 120 VAC power sup- type of system it is attached to. ply to the battery charger. This requires an AC relay with normally closed contacts connected in the circuit •...
20-light Remote Annunciator COMMUNICATION OK RELAY OUTPUT This LED will be on as long as there is proper commu- The RAP will also provide a pair of Normally Open con- nication between the Remote Annunciator Panel and the tacts which will mimic the status of the Audible alarm generator control system.
20-light Remote Annunciator TROUBLESHOOTING GUIDE No LEDs are lit. 1. Check for proper battery supply at J1 pins 3 and 4. • J1 pin 3 should be + Battery (12 or 24 volts). • J1 pin 4 should be – Battery. •...
20-light Remote Annunciator Assembly - Drawing No. 0F0169 ITEM PART NO. QTY. DESCRIPTION 0A6985 PANEL ANNUNCIATOR REAR 0A6388D ASSY, 20LT MODBUS ANNUN G-PNL 040213 PCB SUPPORT SNAP-IN 1/4" 0A6990 SUPPORT, PC BOARD 036901 SCREW PPHM #6-32 X 3/8 0A6988 PANEL ANNUNCIATOR FRONT 0A6733 DECAL ANNUNCIATOR PANEL 061284...
Page 13
20-light Remote Annunciator Assembly - Drawing No. 0F0173 [ OTHER SIDE OF PANEL ] VIEW A - A VIEW B - B ITEM PART NO. QTY. DESCRIPTION 0A7437 PANEL ANNUNCIATOR REAR 0A6388D ASSY, 20LT MODBUS ANNUN G-PNL 040213 PCB SUPPORT SNAP-IN 1/4" 0A6990 SUPPORT, PC BOARD 036901...
Page 14
20-light Remote Annunciator Assembly - Drawing No. 0F0175 REM O TE RELAY PANEL WIRIN G 2 0 LI G H T ITEM PART NO. QTY. DESCRIPTION 0A6985 PANEL ANNUNCIATOR REAR 0A6388D ASSY, 20LT MODBUS ANNUN G-PNL 0A9036B 8CH REM RLY PNL MODBUS RRP G-P 040213 PCB SUPPORT SNAP-IN 1/4"...
Page 15
20-light Remote Annunciator Assembly - Drawing No. 0F0177 [ OTHER SIDE OF PANEL ] 11 12 VIEW A - A VIEW B - B ITEM PART NO. QTY. DESCRIPTION 0A7437 PANEL ANNUNCIATOR REAR 0A6388D ASSY, 20LT MODBUS ANNUN G-PNL 0A9036B 8CH REM RLY PNL MODBUS RRP G-P 040213 PCB SUPPORT SNAP-IN 1/4"...
Page 16
® GENERAC POWER SYSTEMS, INC. P.O. BOX 8 • WAUKESHA, WI 53187 PH: (414) 544-4811 • FA X: (414) 544-4851 Part No. 0F0270 Revision 0 (03/29/04) Printed in U.S.A.
Need help?
Do you have a question about the PM-DCP and is the answer not in the manual?
Questions and answers