Specifications; Operation - Siemens Powers ET 134 Series Technical Instructions

Low temperature detection thermostat

Advertisement

Technical Instructions
Document Number 155-016P25
Rev.1, February, 2000

Specifications

Operation

Page 2
WARNING:
This low temperature detection thermostat is designed for use
only as an operating control. Where an operating control failure
would result in personal injury and/or loss of property, it is the
installer's responsibility to add devices (safety, limit controls) or
systems (alarm, supervisory systems) that protect against, or
warn of control failure.
Switch Action
Range
Maximum bulb temperature
Minimum differential
Sensing element
Bulb length
Reset action
Electrical rating
Weight
Dimensions
Approvals
This thermostat incorporates a temperature sensing element of the vapor-filled type
which actuates a heavy duty contact through a rugged link mechanism.
Any one-foot length of the element subjected to temperatures below the temperature
setting of the thermostat will actuate the thermostat switch mechanism regardless of
the temperature being sensed by the remainder of the element. This makes the
thermostats ideal for protecting large coils where air stratification could cause
freezing conditions in a localized area.
The thermostat has a main and auxiliary contact unit. The main load circuit
(LINE-M2) opens on temperature drop and simultaneously, an auxiliary or alarm
circuit (LINE-Ml) closes on temperature drop.
NOTE:
The reset button must be manually pressed down and released to resume
normal fan system operation.
Low Temperature Detection Cut-out and Alarm Thermostat
Main (LINE-M2) contacts open on
temperature drop, simultaneously auxiliary
contacts close
15 to 55°F (-9 to 13°C)
400°F (204°C)
5°F (2.8°C) Non-adjustable
Vapor filled
1/8-inch OD x 20 feet (6 m)
Manual
See Table 1
2.4 lbs. (1.1 kg)
See Figures 2 and 5
UL file SA 3863
CSA file LR948
Siemens Building Technologies, Inc.