Electrical Ratings; Mounting And Installation - Siemens Powers ET 134 Series Technical Instructions

Low temperature detection thermostat

Advertisement

Low Temperature Detection Cut-out and Alarm Thermostat

Electrical Ratings

Pole
Number
Motor
Rating
AC Full Load
Amps
AC Locked
Rotor Amps
AC Non-Ind
Amps
Pilot Duty-Both Poles
Mounting and
Installation
General Guidelines
Large walk-in Ducts
(Figure 1)
Siemens Building Technologies, Inc.
Line-M2 (Main)
120 V
208 V
240 V
16.0
9.2
8.0
96.0
55.2
48.0
16.0
9.2
8.0
125 VA, 24 to 600 Vac
57.5 VA, 120 to 300 Vdc
Locate the sensing element in the downstream side of the coil.
Locate the case and bellows where the ambient temperature is always warmer than
the set point.
Install the thermostat so that the reset button is readily accessible and the element
bellows points down.
Install as much of the bulb as possible in a horizontal plane. If too much of the bulb is
vertical, it will not operate properly.
Avoid sharp bends or kinks in the sensing element.
1. Attach the mounting bracket to the thermostat with the two round head screws
provided.
2. Mount the two perforated steel strap hangers inside the duct with the wide part of the
hanger strap parallel to the air flow.
3. Drill a hole in the side of the duct. With the bulb still coiled, thread the bulb through
the hole using a rotary movement.
4. Mount the thermostat on the outside of the duct.
5. Carefully uncoil the bulb avoiding sharp bends or kinks in the sensing element.
6. Mount the bulb in a horizontal, serpentine manner, attaching the bulb to the strap as
shown in detail in Figure 1 .
The installation is complete.
NOTE:
For an alternate method of mounting, use coil clips (Part Number 356-115) in
the fins to hold the bulb in a horizontal, serpentine pattern.
Table 1.
Line-M1 (Auxiliary)
277 V
120 V
6.0
36.0
7.2
6.0
Technical Instructions
Document Number 155-016P25
Rev. 1, February, 2000
208 V
240 V
277 V
3.3
3.0
19.8
18.0
6.0
6.0
6.0
Page 3