Ariston EGIS PREMIUM S 25 Installation And Servicing Instructions page 48

Condensing wall-hung gas boiler

Advertisement

settings - adjustment - problem identifi cation menus
description
notes
423
Parallel curve shift Zone 1
Off set
To adapt the heating curve to the system requirements, shift
the curve in parallel so that the calculated fl ow temperature is
modifi ed, in addition to the room temperature.
Access the parameter and press buttons 1 "+" or "-"
temperature regulation is activated to shift the curve upwards
or downwards.
Each step represents a fl ow temperature increase/decrease in
relation to the set-point value.
- from -14 to +14 °C (high temperature)
- from - 7 to + 7 °C (low temperature)
Warning!
The curves can be shifted upwards or downwards without
accessing the parameter, using buttons 1 "+" or "-"
425
Maximum Central Heating
Temperature Zone 1
426
Minimum Central Heating
Temperature Zone 1
701 Air purge Function
822 Fan Speed - x100 RPM
831 Flow Heating temperature (°C)
832 Return Heating temperature (°C)
842 D.H.W. Inlet Temperature
Display only with Solar Kit or external storage Kit
48
value
from - 14 to + 14 (°C)
0
(high temperature)
from - 7 to + 7 (°C)
0
(low temperature)
while
from 35 to 85 °C
82
(Param. 420 = 1)
from 20 to 45 °C
45
(Param. 420 = 0)
from 35 to 85 °C
40
(Param. 420 = 1)
from 20 to 45 °C
25
(Param. 420 = 0)
Press MODE button to
active

Advertisement

loading

This manual is also suitable for:

Egis premium s 31