Remove the packing following the instructions given in the "Packaging and storing" section and, using a fork lift truck,
lift the unit and position in the place desired . While moving the unit, keep it upright without tilting it . High protection
against the transmission of vibrations is achieved by placing appropriate dowels made of impact-resistant material
(neoprene etc .) between the support feet of the unit and the floor . For this purpose, the distances for the positioning of
vibration dampers are listed below . In any event, consult the specialized catalogues when choosing the support feet .
Model
9-12
Ref .
L
762
l1
111
l2
540
l3
111
l4
68
D
257
d1
286

CONDENSATION DRAIN KIT FOR OUTDOOR UNIT

In the outdoor units with heat pump, condensation is created
when running in heating mode . In this case it may be necessary
to convey the condensation towards a drain .
To do so, proceed as follows:
1 . Fix the supplied fitting (1-Fig . 1) in the appropriate hole (2-Fig .
1) on the base of the outdoor unit . The fastening is carried out by
inserting the shaped part of the fitting in the hole .
2 . Connect the fitting (1-Fig . 2) to a sufficiently resistant rubber
hose (2-Fig . 2) (so that it is not deformed or throttled in any way) .
3 . Secure it with a hose clip and route it to an appropriate drain .
4 . Make sure that the pipe slopes enough to allow the
condensation to flow down naturally .
5 . Check the efficiency of the drain by pouring a small amount
of water directly into the tray of the outdoor unit .
Note: The kit is supplied with the machine .
INSTALLATION
18
22
U .M
820
890
mm
135
165
mm
550
560
mm
135
165
mm
70
70
mm
310
340
mm
344
364
mm
2
1
Fig . 1
Fig . 2
11