Page 2
Documents released in PDF electronic format may be printed by end-users for their own use using a printer such as an inkjet or laser device. Authorized distributors of Delta Controls Inc. products (Delta Partners) may print PDF documents for their own internal use or for use by their customers. Authorized Delta Partners may engage a printing or copying company to produce copies of released PDF documents with the prior written permission of Delta Controls Inc.
Contents About the eZV-440 ........................4 About This Guide ......................... 4 Upgrading From Older Firmware Versions................. 4 About the Configuration Graphic ....................5 Downloading the Configuration Graphic ..................5 Installing the Configuration Graphic ................... 5 Opening the Configuration Graphic ..................... 6 Working With the Configuration Graphic ..................7 Selecting Between Multiple Controllers .................
Page 4
Space Temperature Setpoints ....................42 Discharge Air Temperature Limiting Setpoints ..............43 VAV / VVT Setpoints .........................43 Setpoint Range Limiting ......................44 Controllers Tab ........................45 Sequences of Operations ......................47 Setpoint Control .........................47 eZV-440 Version 2.1 Application Guide Page 2 of 67 Document Edition 2.5...
Page 5
Device Instance/BACnet Address Object ...................62 Appendix B: Control Types ....................... 63 Appendix C: Open Source Licensing ..................64 lwIP .............................64 ST Microelectronics ........................65 Document Revision History ...................... 66 Page 3 of 67 eZV-440 Version 2.1 Application Guide Document Edition 2.5...
The configuration graphic version referenced in this guide is B-169041.1. For help about the eZV-440 configuration page in enteliWEB 4.1 and higher, go to the online help in enteliWEB. enteliWEB users require the applicable object permissions to change the settings on the configuration page.
Downloading the Configuration Graphic You can download the configuration graphic from the eZV-440 product web page on the Delta Controls Support web site (support.deltacontrols.com) and install it on your operator workstation. The version referenced in this guide is B-169041.1.
Method 1 (Recommended) 1. In the left window of the ORCAview navigator, right-click on the eZV-440 controller and click Open. If this is your first time using the configuration graphic, the DEV object dialog opens.
A new graphic window opens. You can access all the configuration files from this window. 2. In the numerical field at the top of the window, enter the BACnet address of the eZV-440 controller you want to configure and click Connect.
In the example below, when you right-click on the number 1 and select Open SpaceTemp_AI1, the AI1 object dialog opens onscreen. eZV-440 Version 2.1 Application Guide Page 8 of 67 Document Edition 2.5...
Configurable and Programmable eZV Controllers Configurable and Programmable eZV Controllers The eZV-440 controller is designed to work predictably for typical VAV and VVT applications with minimal setup. Using the configuration graphic, objects and setpoints are entered into the algorithm and written to the appropriate preset objects (100-199 range, 1000+ range for LINKnet device configuration) in the factory controller database.
(Delta Exchange Remote or DER objects). Other types of Data Exchange initiating request types are not supported. The Description tab on the DES object for the eZV-440 controller lists the number of DER and DEL requests that are in use.
User-defined User-defined User-defined User-defined The eZV-440 trend logs also support Historian archiving. The enteliZONE controllers don’t support buffer full notification events so make sure the Historian update interval is frequent enough to avoid missing samples. Page 11 of 67 eZV-440 Version 2.1 Application Guide...
The Call Statement is not used in the programmable eZVP-440 controllers. Unlike other programmable Delta Controls controllers, the 3 programs in the eZVP-440 are automatically scanned. The eZVP-440 controller scan rate is also designed to be a constant 10 scans/second.
Page 15
CurrentHeatingSetpoint Manager AV801 CurrentCoolingSetpoint Demand Controls the CO2 levels in the space. See the Demand Control AV813 DemandCtrlVent Control Ventilation sequence of operation for more information. Ventilation Manager Page 13 of 67 eZV-440 Version 2.1 Application Guide Document Edition 2.5...
Page 16
Hydronic and Electric Duct BV800 Air Flow Status MV801 VAVDuct1BoxMode AV813 DemandCtrlVent Point(s) in each algorithm manager box can be used to override the algorithm manager Relationship between points eZV-440 Version 2.1 Application Guide Page 14 of 67 Document Edition 2.5...
Possible reasons for a failed airflow zero include sensor problems or the inability of the damper to fully close. eZV-440 Version 2.1 Application Guide Page 16 of 67 Document Edition 2.5...
Verify that the heater is turned on. If the heater doesn’t turn on, adjust the airflow safety or raise the heating minimum setpoint so that the safety contact is made and the duct heater is allowed to run. Page 17 of 67 eZV-440 Version 2.1 Application Guide Document Edition 2.5...
You can change this name but you are limited to 36 characters. Model Number Displays the controller’s Delta Controls model number. This is a read-only field. Firmware Version Displays the controller’s firmware version. This is a read-only field. Firmware Build Displays the controller’s firmware build number.
BACnet address also becomes read-only. To manually enter a new address, clear the DNA box. Delta Controls products have the option to use DNA or Derived Network Addressing, a system of organizing and configuring controllers in a network. When DNA is enabled,...
Displays the temperature units used by the eZV-440 controller. Select between Celsius Temperature Units and Fahrenheit. Displays the airflow units used by the eZV-440 controller. Select between CFM, l/s or Airflow Units If this controller reports to a parent controller, enter the parent’s BACnet address in this field.
Local Inputs Tab Local Inputs Tab Inputs 1 to 4 on the eZV-440 controller are physical Universal Inputs. This section describes how to configure these Universal Inputs for the following cases (click the link to go to the specific section): Hardwired temperature sensor •...
Page 24
Multiple SpaceTemp Inputs You can set up multiple SpaceTemp inputs and by default the algorithm will calculate the average of all inputs and assign that value to the AV1 object. eZV-440 Version 2.1 Application Guide Page 22 of 67 Document Edition 2.5...
SpcTemp+OccOvrdButton_ This can be a normally open contact wired in parallel or a normally closed contact wired in series with the temperature sensor. Page 23 of 67 eZV-440 Version 2.1 Application Guide Document Edition 2.5...
2. Next to the input number that you’ve assigned to the sensor, in the Function field, select SpaceCO2_. The default option in the Action/Scale column is CO2 0-2000ppm. eZV-440 Version 2.1 Application Guide Page 24 of 67 Document Edition 2.5...
Creating a binary input that will be used for BinaryMUX monitoring and will not be used by the algorithm in the controller. Page 25 of 67 eZV-440 Version 2.1 Application Guide Document Edition 2.5...
± offset in the OccSetpointOffsetRange field. Set Up an Airflow Sensor Input 6 in the graphic is reserved for the eZV-440 controller’s onboard differential pressure sensor. To set up the airflow sensor on the eZV-440 controller: 1.
Local Outputs Tab Local Outputs Tab Outputs 1 to 4 on the eZV-440 controller are physical Universal Outputs. Outputs 5 and 6 are used by the actuator connector (1 Universal Output, 1 TRIAC Output). This section describes how to set up these physical outputs on the Local Outputs tab in this configuration graphic.
Set Up an Output This section describes how to set up an output device that you have connected to one of the controller’s Universal Outputs 1 to 4. The eZV-440 controller supports up to 3 stages of heat (Heat1, Heat2 and Heat3).
Page 31
If you are setting up a parallel fan, select Always Intermittent. In occupancy modes where the fan is not running constantly, the algorithm assumes the fan is running intermittently. Page 29 of 67 eZV-440 Version 2.1 Application Guide Document Edition 2.5...
Page 32
100%. When you select a binary control type for a single or multi-speed fan, this field displays the maximum supported fan speed. eZV-440 Version 2.1 Application Guide Page 30 of 67 Document Edition 2.5...
6. If you are setting up a tri-state actuator with damper feedback, set up damper feedback on the Local Inputs tab in the configuration graphic. Page 31 of 67 eZV-440 Version 2.1 Application Guide Document Edition 2.5...
LINKnet I/O Tab The eZV-440 controller is designed to work with a DNS-24L or eZNS network sensor on its LINKnet port. This section describes how to set up one of these network sensors using the LINKnet I/O tab in this configuration graphic.
Note: Dehumidification is not available with VVT and VAV applications. The input object AI1003 is created for monitoring MonitoringOnly only. Dehumidification will not be enabled in this case. Page 33 of 67 eZV-440 Version 2.1 Application Guide Document Edition 2.5...
Page 36
This setting allows the use of momentary contact style occupancy signals. If you are using maintained-contact occupancy devices, enter zero in this field. In this case, occupancy statue is only based on contact position. eZV-440 Version 2.1 Application Guide Page 34 of 67 Document Edition 2.5...
Page 37
8 buttons, button areas are merged together and counted as one (see the examples below). Button Overlay Selection Summary For more information about the button overlays, see the document on the Delta Controls support web site support.deltacontrols.com. Page 35 of 67 eZV-440 Version 2.1 Application Guide Document Edition 2.5...
Page 38
Celsius and the temperature in Fahrenheit Decrease the temperature setpoint by 0.5 degrees with each buttonpress. The 0.5 degree amount cannot be changed in the eZV-440 configurable model. In the programmable model, TempDown_ this setting can be overridden using GCL.
Page 39
Select this option if you want to: eZNS button Increase the temperature setpoint by 0.5 degrees with each buttonpress. The 0.5 degree amount cannot be changed in the eZV-440 configurable model. In the programmable model, this setting TempUp_ can be overridden using GCL.
Page 40
The offset that you can enter to adjust the occupied heating and cooling setpoints. The SetpointOffset_ range available for this offset is determined by the OccSetpointOffsetRange field on the Setpoints tab. eZV-440 Version 2.1 Application Guide Page 38 of 67 Document Edition 2.5...
You can program the functionality of each button on the network sensor using the configuration graphic. The buttons on the DNS-24L are numbered 1 to 4 in the graphic. Page 39 of 67 eZV-440 Version 2.1 Application Guide Document Edition 2.5...
Page 42
Celsius and the temperature in Fahrenheit. Decrease the temperature setpoint by 0.5 degrees with each buttonpress. The 0.5 degree amount cannot be changed in the eZV-440 configurable model. In the programmable model, TempDown_ Button 3 this setting can be overridden using GCL.
Page 43
Select this option if you want to: DNS-24L button Increase the temperature setpoint by 0.5 degrees with each buttonpress. The 0.5 degree amount cannot be changed in the eZV-440 configurable model. In the programmable model, this setting TempUp_ Button 4 can be overridden using GCL.
Unoccupied Cooling Setpoint: When the controller is in unoccupied mode, UnOccCoolingSetpoint cooling is turned on when the space temperature rises above this setpoint. eZV-440 Version 2.1 Application Guide Page 42 of 67 Document Edition 2.5...
Flow Factor: This is the coefficient used to convert airflow pressure into FlowFactor CFM. AirflowFailureSetpoint Airflow Failure Setpoint: The failure setpoint for airflow pressure. CoolingMinimum The minimum cooling airflow setpoint. Page 43 of 67 eZV-440 Version 2.1 Application Guide Document Edition 2.5...
Setpoint Range Limiting The user setpoints are range limited as follows: Minimum Value Maximum Value Setpoint °C (°F) °C (°F) OccHeatingSetpoint OccCoolingSetpoint 10.0 (50) 30.0 (86) UnOccHeatingSetpoint UnOccCoolingSetpoint eZV-440 Version 2.1 Application Guide Page 44 of 67 Document Edition 2.5...
The reset rate determines how fast the controller bias is adjusted to make the necessary correction so that there is no offset between the signal and the setpoint. Page 45 of 67 eZV-440 Version 2.1 Application Guide Document Edition 2.5...
Page 48
VAV and VVT systems. For more information about Proportional-Integral-Derivative control, see Probing the Depths of PID Control webinar on the Delta Controls Support web site. eZV-440 Version 2.1 Application Guide Page 46 of 67 Document Edition 2.5...
Eco mode and standby setbacks also are limited to the range between unoccupied heating and cooling setpoints. The absolute minimum value for all occupied and unoccupied setpoints is 10°C (50°F). The absolute maximum value is 30°C (86°F). Page 47 of 67 eZV-440 Version 2.1 Application Guide Document Edition 2.5...
Occupied and Standby modes in response to any event-based occupancy signals. When scheduling is off, event-based occupancy signals cause the space to switch between Unoccupied and Unoccupied Override modes. eZV-440 Version 2.1 Application Guide Page 48 of 67 Document Edition 2.5...
Page 51
= Occupied Cooling Setpoint + Occupied Setpoint offset + Eco Mode Setback Occupant setpoint sits between the occupied heating and cooling setpoints. The occupied setpoint offset is restricted to be within the occupied setpoint offset range. Page 49 of 67 eZV-440 Version 2.1 Application Guide Document Edition 2.5...
CO • occupancy signal if active is cancelled. The upper range of this setpoint is set at 100 ppm below the CO2OccOnSetpoint threshold. eZV-440 Version 2.1 Application Guide Page 50 of 67 Document Edition 2.5...
If outdoor air temperature (AV9) rises above outdoor air temperature heating lockout setpoint (OATHtgLockout), then all heating is disabled. The outdoor air temperature will have to drop by 1.0 °C below this setpoint before the heating is re-enabled. Page 51 of 67 eZV-440 Version 2.1 Application Guide Document Edition 2.5...
HeatCmd or AutoHeat (hot As the Airflow Demand increases from 0 to 100%, the Heating Demand air in the duct) airflow setpoint increases from the HeatingMinimum to the HeatingMaximum setpoint. eZV-440 Version 2.1 Application Guide Page 52 of 67 Document Edition 2.5...
Page 55
The damper is the first stage of cooling. As the Airflow CoolCmd or AutoCool (cold Demand increases from 0 to 100%, the airflow setpoint Cooling Demand air in the duct) increases from the CoolingMinimum to the CoolingMaximum setpoint. Page 53 of 67 eZV-440 Version 2.1 Application Guide Document Edition 2.5...
The CO demand is reflected in the demand control ventilation (AV813) object. The algorithm determines the airflow setpoint needed to meet this demand. The demand increases when the eZV-440 Version 2.1 Application Guide Page 54 of 67 Document Edition 2.5...
Note with parallel fan VAV systems, heating airflow is provided by the fan and not the primary air. So the heating minimum and maximum airflow settings are generally not used and should be set to be equal to the cooling minimum airflow setpoint. Page 55 of 67 eZV-440 Version 2.1 Application Guide Document Edition 2.5...
Unoccupied and Standby modes the fan does not run and only runs when there is a heating demand. Duct pressure drops below 2Pa for longer than 10 seconds. • eZV-440 Version 2.1 Application Guide Page 56 of 67 Document Edition 2.5...
Otherwise the difference in airflows will be blown out through the induction port into the ceiling plenum. Page 57 of 67 eZV-440 Version 2.1 Application Guide Document Edition 2.5...
Appendix A: Database Configuration Objects The following table lists the database objects used to configure the eZV-440 controller. Programs are prevented from writing to algorithm configurable MV objects, I/O configurable MV objects and network setting variables. These include MV110-147 and MV1001-1006. See the eZV-440 controller 2.1 release notes for more information.
Used to display the occupancy icon Not Used, Off, On OccIndicator MV806 on the network sensor LCD screen. Default = Not Used *Available only with eZVP-440 programmable model eZV-440 Version 2.1 Application Guide Page 60 of 67 Document Edition 2.5...
Discharge air temperature high DATHiLimitSetpoint AV161 Default = 35 °C limit setpoint Discharge air temperature high DATHiLimitPropBand AV162 Default = 5 °C limit proportional limit band Page 61 of 67 eZV-440 Version 2.1 Application Guide Document Edition 2.5...
The BACnet address is a unique address given to every controller and device in a Delta network. In the eZ-440 controller firmware version 2.01, you can set or change the eZV-440 controller’s BACnet address by writing to the AV97 object (BACnetAddress).
Appendix B: Control Types Appendix B: Control Types On the Local Outputs tab, control types refer to the methods of control used on the output device signal. The eZV-440 controller supports 5 control types: Control Types Description Analog Provides modulating control using a 0-10V analog signal...
IN CONTRACT, STRICT LIABILITY, OR TORT (INCLUDING NEGLIGENCE OR OTHERWISE) ARISING IN ANY WAY OUT OF THE USE OF THIS SOFTWARE, EVEN IF ADVISED OF THE POSSIBILITY OF SUCH DAMAGE. Page 65 of 67 eZV-440 Version 2.1 Application Guide Document Edition 2.5...
Corrections to series fan sequences. Custom buttons for LINKnet devices. Corrected the setpoint calculations February 17, 2017 Norlinda Ghazali in the Occupancy Modes section under Sequence of Operations. eZV-440 Version 2.1 Application Guide Page 66 of 67 Document Edition 2.5...
Page 69
Document Revision History Page 67 of 67 eZV-440 Version 2.1 Application Guide Document Edition 2.5...
Need help?
Do you have a question about the eZV-440 and is the answer not in the manual?
Questions and answers