Electrical data

STANDARD MOTOR UNITS WITHOUT ELECTRICAL CONVENIENCE OUTLET
NOMINAL
UNIT
VOLTAGE
(V-Ph-Hz)
208/230-1-60
208/230-3-60
48HJE/HJF004
(3 Tons)
460-3-60
575-3-60
208/230-1-60
208/230-3-60
48HJD/HJE/HJF005
(4 Tons)
460-3-60
575-3-60
208/230-1-60
208/230-3-60
48HJD/HJE/HJF006
(5 Tons)
460-3-60
575-3-60
208/230-3-60
48HJD/HJE/HJF007
460-3-60
(6 Tons)
575-3-60
208/230-3-60
48HJD/HJE/HJF008
460-3-60
(7
1
/
Tons)**
2
575-3-60
208/230-3-60
48HJD/HJE/HJF009
460-3-60
1
(8
/
Tons)**
2
575-3-60
208/230-3-60
48HJD/HJE/HJF012
460-3-60
(10 Tons)**
575-3-60
208/230-3-60
48HJD/HJE014
460-3-60
1
(12
/
Tons)**
2
575-3-60
LEGEND
FLA
— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
IFM
— Indoor (Evaporator) Fan Motor
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC
— National Electrical Code
OFM
— Outdoor (Condenser) Fan Motor
RLA
— Rated Load Amps
UL
— Underwriters' Laboratories
*Used to determine minimum disconnect per NEC.
†Fuse or HACR circuit breaker per NEC.
**Units have 2 condenser-fan motors.
VOLTAGE
COMPRESSOR
RANGE
(each)
Min
Max
RLA
LRA
187
254
16.0
88.0
187
254
10.3
77.0
414
508
5.1
39.0
518
632
4.2
31.0
187
254
23.7
129.0
187
254
13.5
99.0
414
508
7.4
49.5
518
632
5.8
40.0
187
254
28.8
169.0
187
254
17.3
123.0
414
508
9.0
62.0
518
632
7.1
50.0
187
254
20.5
156.0
414
508
9.6
70.0
518
632
7.7
56.0
187
254
12.4
88.0
414
508
6.4
44.0
518
632
4.8
34.0
187
254
15.0
99.0
414
508
8.2
49.5
518
632
5.8
40.0
187
254
17.3
123.0
414
508
9.0
62.0
518
632
7.1
50.0
187
254
19.0
156.0
414
508
9.0
70.0
518
632
7.4
54.0
OFM
COMBUSTION
IFM
(each)
FAN MOTOR
FLA
FLA
FLA
0.7
4.9
.57
0.7
4.9
.57
0.4
2.2
.30
0.4
2.2
.30
0.7
4.9
.57
0.7
4.9
.57
0.4
2.2
.30
0.4
2.2
.30
1.5
8.8
.57
1.5
5.8
.57
0.8
2.6
.30
0.8
2.6
.30
1.4
5.8
.57
0.6
2.6
.30
0.6
2.6
.30
1.4
7.5
.57
0.7
3.4
.30
0.7
3.4
.30
1.4
7.5
.57
0.7
3.4
.30
0.7
3.4
.30
1.4
10.6
.57
0.7
4.8
.30
0.7
4.8
.30
1.4
15.0
.57
0.7
7.4
.30
0.7
7.4
.30
NOTES:
1. In compliance with NEC requirements for multimotor and combina-
tion load equipment (refer to NEC Articles 430 and 440), the over-
current protective device for the unit shall be fuse or HACR
breaker. The UL, Canada units may be fuse or circuit breaker.
2. Electrical data based on 95 F ambient outdoor-air temperature
± 10% voltage.
MINIMUM UNIT
POWER
DISCONNECT
SUPPLY
SIZE*
MCA
MOCP
FLA
25.6/25.6
35/35†
25/25
101/101
18.5/18.5
25/25†
18/18
9.0
15†
9
7.3
15†
7
35.2/35.2
45/45†
34/34
142/142
22.5/22.5
30/30†
22/22
112/112
11.9
15†
12
9.3
15†
9
46.3/46.3
60/60†
45/45
216/216
28.9/28.9
35/35†
28/28
168/168
14.7
20†
14
11.6
15†
11
32.8/32.8
40/40†
32/32
200/200
15.2
20†
15
12.2
15†
13
38.2/38.2
45/45†
40/40
242/242
19.2
25†
20
14.6
20†
16
44.1/44.1
50/50†
46/46
264/264
23.3
30†
24
16.9
20†
18
52.3/52.3
60/60†
55/55
337/337
26.5
35†
26
20.9
25†
22
60.6/60.6
70/70†
64/64
426/426
29.1
30†
31
23.7
30†
25
LRA
90/90
46
36
56
45
84
67
92
78
121
95
132
107
171
136
197
154
51