Carrier Weathermaster 48HJD Series Product Data page 48

Single-package rooftop units high-efficiency electric cooling/ gas heating
Table of Contents

Advertisement

Performance data (cont)
UNIT
UNIT
48HJ
PHASE
004
Three
005
Three
006
Three
007
Three
008,009
Three
012
Three
LEGEND
Bhp — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the
motors can be utilized with confidence. Using your fan motors up to the ratings shown in this table will not
result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
OUTDOOR SOUND POWER (TOTAL UNIT)
ARI
UNIT
RATING
48HJ
63
(Bels)
004,005
7.6
55.9
006,007
8.0
59.1
008,009
8.2
62.2
012
8.4
64.6
014
8.6
63.7
LEGEND
ARI
— Air Conditioning and Refrigeration Institute
Bels — Sound Levels (1 bel = 10 decibels)
ECONOMIZER STATIC PRESSURE DROP (in. wg)
UNIT
900
1200
Durablade
0.05
0.05
EconoMi$er
0.09
ECONOMIZER STATIC PRESSURE DROP (in. wg)
UNIT
2200
2500
Durablade
.02
.02
EconoMi$er
48
EVAPORATOR-FAN MOTOR DATA — HIGH-STATIC MOTORS
MAXIMUM
CONTINUOUS BHP*
2.40
2.40
2.90
2.90
4.20
5.25
OCTAVE BANDS
125
250
500
1000
66.0
64.0
66.2
68.4
68.9
68.7
71.9
74.0
69.3
71.5
74.7
76.2
71.1
73.3
76.9
77.6
69.9
72.5
78.2
81.1
48HJ004-007
CFM
1400
1600
1800
0.05
0.05
0.05
0.12
0.15
0.19
48HJ008-014
CFM
3000
3500
4000
0.030
0.040
0.05
0.125
0.180
0.27
MAXIMUM
OPERATING WATTS*
2120
2120
2615
2615
3775
4400
2000
4000
8000
64.5
61.7
57.3
68.9
65.7
59.0
72.9
68.7
61.5
73.7
70.6
63.7
77.3
73.3
66.8
2000
2200
2400
2600
0.05
0.05
0.05
0.05
0.24
0.29
0.35
4500
5000
5500
6000
0.06
0.07
0.08
0.09
0.34
0.40
MAXIMUM
UNIT VOLTAGE
AMP DRAW
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
208/230
460
575
6.4
2.9
2.9
6.4
2.9
2.9
7.9
3.6
3.6
6.4
3.6
3.6
12.6
5.7
5.7
15.0
7.4
7.4

Hide quick links: