Appendix D.5. BACnet Specific Statistics

Stat
A "who-is" link control message was
Link Control
send or received.
Unsupported
A request for an unsupported
Properties
property was received.
Data was requested but the response
would have exceeded the maximum
Segmentation
size of the APDU and could not be
Not Supported
sent using an un-segmented
message.
Invoke ID of a reply did not match the
Sequence Error
Invoke ID of the poll.
Write
Access
A write to an object was denied.
Denied
A BACnet Service was denied
Exception Errors
because it is not supported.
Description
Page 34 of 34
BACnet PTP Serial Driver Manual
Resolution
It is normal to receive a few link control
messages. If the number is higher than the
transmit/receive messages, however, there
may be a problem with lost communications.
This is not an error. BACnet clients often poll
all properties of a particular object to
determine which properties are supported.
This is not an error – the BACnet client will
use a different method to read data from the
FieldServer.
You should not see this message. It normally
indicates a configuration error.
This typically happens when trying to write to
an Input Object that is not Out-Of-Service. It
is not possible to write to Input Objects.
This may be a problem on the Client system.
Consult the PIC statement to determine what
services are supported.