Honeywell Notifier AMPS-24/E Manual page 19

Table of Contents

Advertisement

Cabinet Wiring Examples
TB2 - Secondary Power 5V and
24V Auxiliary outputs.
Power-limited (Class 2).
TB1 - AC Primary
Power Wiring -
Nonpower-limited and
supervised
TB3 - Nonpower-limited
and supervised
Grounding
Wire
Figure 2.8 BB-100 Cabinet: Power-limited (Class 2) Wiring Example with Two Battery Wiring
TB1 - AC Primary
Power Wiring -
Nonpower-limited
and supervised.
TB3 -
Nonpower-limite
d and
supervised.
Grounding
Wire
Figure 2.9 BB-200 Cabinet: Power-limited (Class 2) Wiring Example with Four Battery Wiring
AMPS-24 Manual — P/N 51907:J2 02/26/2014
TB1 - Main 24V power to panel.
Power-limited (Class 2).
TB2 - SLC Circuit Wiring - Power-limited
(Class 2) and supervised.
TB4 - Trouble Bus Wiring - Power-limited
(Class 2) and non-supervised.
TB2 - Secondary Power
5V and 24V Auxiliary
outputs. Power-limited
(Class 2).
The BB-100 cabinet must be
located less than 20 feet (6.1
m) from the enclosure
housing the control panel and
all connections must be
contained in conduit.
TB3 - 24V Auxiliary power.
Power-limited (Class 2).
TB1 - Main 24V power to panel. Power-limited (Class 2).
TB2 - SLC Circuit Wiring - Power-limited (Class 2) and
supervised.
TB4:Trouble Bus Wiring - Power-limited (Class 2),
non-supervised.
Installation
TB3 - 24V Auxiliary
power. Power-limited
(Class 2).
The BB-200 cabinet must
be located less than 20
feet (6.1 m) from the
enclosure housing the
control panel and all
connections must be
contained in conduit.
19