Handling And Placement Of Evaporator Coil In Walk-In; Evaporator And Drain Line Installation Instructions - Standex Master-Bilt B-SERIES Installation & Operation Manual

Condensing unit and refrigeration system
Table of Contents

Advertisement

II. Handling and Placement of Evaporator Coil in Walk-In
To minimize damage to the evaporator coil, it is recommended that the carton (or crate) not be removed
until the evaporator coil is moved close to its final location. When the container is removed from the
evaporator coil, extreme care must be used when lifting and mounting to the ceiling, to prevent sheet
metal damage.
EVAPORATOR INSTALLATION INSTRUCTIONS
A. Do not install the evaporator too close to door openings to prevent icing problems.
B. Minimum clearance between evaporator and the walls is equal to or greater than the coil height
for proper air flow and service access.
C. Refer to the evaporator coil drawing dimension for mounting holes location.
D. Install washers and secure with nuts. Tighten until the coil is firm against the ceiling. The
evaporator coil must be level.
5/16 Rev. B 57-02497
9