PRE-INSTALLATION INSTRUCTIONS
I. General Information
Please read this manual prior to installing your Master-Bilt
good refrigeration practice and should be used as a guide for installation and operation.
To complete the installation, please records the data requested on the Installation Data form on page 35
of the manual and return this manual to the owner.
II. Delivery Inspection
You are responsible for filing all freight claims with the delivering truck line. Inspect all cartons and
crates for damage as soon as they arrive. If damage is noted to shipping crates, cartons or if a shortage is
found; note this on the bill of lading (all copies) prior to signing.
If damage is discovered when the cabinet is uncrated, immediately call the delivering truck line and
follow up the call with a written report indicating concealed damage to your shipment. Ask for an
immediate inspection of your concealed damage item. Crating material MUST be retained to show the
inspector from the truck line.

INSTALLATION INSTRUCTIONS

I. Handling and Placement of Condensing Unit
To minimize damage to the unit housing, it is recommended that the crate not be removed until the unit
is moved to its final location.
The following should be considered when placing the unit:
A. The condenser coil (air inlet) should not be located so as to restrict air flow into the coil. A
minimum of 12" is required (18" is preferred) between the face of the coil and a wall or other
vertical obstruction.
B. A minimum of 6" is required on the sides to allow access to the housing clamps.
C. A minimum of 24" is required on the louvered end ( air outlet) for clearance when opening
housing and for ease of maintenance.
D. Do not position multiple units so that the air discharge of one is into the condenser air intake of
another.
Holes are provided in the base supports for mounting bolts and for bridle lift rods.
For indoor mounting, motor rooms should be provided with fans designed to move 1000 cfm of air per
ton of refrigeration.
5/16 Rev. B 57-02497
®