4.2.6.
Analog Value Object Instance
The analog value objects allow to monitor drive status such as output frequency, current
and voltage. Additionally, drive speed reference can be set as Analog Value #16.
Binary
Object Name
Value ID
#0
OUTPUT SPEED
#1
OUTPUT FREQ
#2
DC BUS VOLT
#3
OUTPUT VOLT
#4
CURRENT
#5
TORQUE
#6
POWER
#7
DRIVE TEMP
#8
KWH (R)
#10
PRC PID FBCK
#14
RUN TIME
#16
INPUT REF 1
#18
LAST FLT
#19
PREV FLT 1
#20
PREV FLT 2
#23
ACCEL1 TIME *
#24
DECEL1 TIME *
#25
MBOX PARAM
#26
MBOX DATA
* Avoid frequently writing to these objects, because the Life of EEPROM is approximately 100,000 times.
R=Read-only, W=Writable, C=Commandable.
Description
-1
Output speed[min
](Calculate from fd00)
Output frequency[Hz](fd00)
DC bus voltage (Calculate from fe04)
Motor voltage(Calculate from fe05)
Motor current(Calculate from fe03)
Motor Torque(fe18)
Motor Power(Calculate from fe30)
100%=√3×VSD rate voltage ×Motor rate current
Drive Thermal State(fd24)
OL1 will be caused, if this value reaches 100%,
Energy counter(Calculate from fd76,fd77)
PID regulator feedback (fe22 / vl*100.00)
Cumulate operation time (fe14)
Speed reference (fa07/vl*100)
Current fault code(fc90)
Past fault code(most recent fault)(fe10)
Past fault code(fault before most recent)(fe11)
Acceleration time(acc)
Deceleration time(dec)
Parameter number
Parameter value
- 14 -
E6581440
UNIT
Access
-1
min
R
Hz
R
V
R
V
R
A
R
%
R
%
R
%
R
KWH
R
%
R
hour
R
%
C
-
R
-
R
-
R
SEC
W
SEC
W
-
W
-
W