Analog Value Object Instance - Toshiba TOSVERT BCN001Z Function Manual

Vf-ps1 series bacnet option unit
Table of Contents

Advertisement

4.2.6.

Analog Value Object Instance

The analog value objects allow to monitor drive status such as output frequency, current
and voltage. Additionally, drive speed reference can be set as Analog Value #16.
Binary
Object Name
Value ID
#0
OUTPUT SPEED
#1
OUTPUT FREQ
#2
DC BUS VOLT
#3
OUTPUT VOLT
#4
CURRENT
#5
TORQUE
#6
POWER
#7
DRIVE TEMP
#8
KWH (R)
#10
PRC PID FBCK
#14
RUN TIME
#16
INPUT REF 1
#18
LAST FLT
#19
PREV FLT 1
#20
PREV FLT 2
#23
ACCEL1 TIME *
#24
DECEL1 TIME *
#25
MBOX PARAM
#26
MBOX DATA
* Avoid frequently writing to these objects, because the Life of EEPROM is approximately 100,000 times.
R=Read-only, W=Writable, C=Commandable.
Description
-1
Output speed[min
](Calculate from fd00)
Output frequency[Hz](fd00)
DC bus voltage (Calculate from fe04)
Motor voltage(Calculate from fe05)
Motor current(Calculate from fe03)
Motor Torque(fe18)
Motor Power(Calculate from fe30)
100%=√3×VSD rate voltage ×Motor rate current
Drive Thermal State(fd24)
OL1 will be caused, if this value reaches 100%,
Energy counter(Calculate from fd76,fd77)
PID regulator feedback (fe22 / vl*100.00)
Cumulate operation time (fe14)
Speed reference (fa07/vl*100)
Current fault code(fc90)
Past fault code(most recent fault)(fe10)
Past fault code(fault before most recent)(fe11)
Acceleration time(acc)
Deceleration time(dec)
Parameter number
Parameter value
- 14 -
E6581440
UNIT
Access
-1
min
R
Hz
R
V
R
V
R
A
R
%
R
%
R
%
R
KWH
R
%
R
hour
R
%
C
-
R
-
R
-
R
SEC
W
SEC
W
-
W
-
W

Advertisement

Table of Contents
loading

Table of Contents