4.2.4.

Analog Input Object Instance

The analog input objects allow to monitor inverter analog input terminal level.
These objects only read inverter parameters those are prepared as read only monitor
parameters(from fe35 to fe39).
These objects present-value unit is "%" unit, and present-value=100.0% mean analog
input terminals are a full range input level.
Instance ID
Analog Input #0
Analog Input #1
Analog Input #2
Analog Input #3
Analog Input #4
Analog Input #3,#4 :
R=Read-only, W=Writable, C=Commandable.
4.2.5.

Analog Output Object Instance

The analog output objects allow to control inverter analog(AM,FM,...) output levels, and
also can be used priority-array and relinquish-default property.
These objects only write to inverter parameters(
meter function selection parameters(see below table) to 31.
Instance ID
Analog output #0
Analog output #1
Analog output #2
Analog output #3
Analog output #2,#3 :
R=Read-only, W=Writable, C=Commandable.
Object Name
Description
ANALOG INPUT 1
RR/S4 analog input level.
ANALOG INPUT 2
VI/II analog input level.
ANALOG INPUT 3
RX analog input level.
ANALOG INPUT 4
AI1 analog input level.
ANALOG INPUT 5
AI2 analog input level.
These are enabled with ETB004Z(Expansion IO card option).
Object Name
Description
AO1 COMMAND
Set fmsl to 31, in order to use inverter FM terminal.
AO2 COMMAND
Set amsl to 31, in order to use inverter AM terminal.
AO3 COMMAND
Set f672 to 31, in order to use MON1 terminal on
the expansion IO card option.
AO4 COMMAND
Set f674 to 31, in order to use MON2 terminal or
pulse output terminal on the expansion IO card option.
These are enabled with ETB004Z(Expansion IO card option).
fa51
- 13 -
E6581440
(fe35)
(fe36)
(fe37)
(fe38)
(fe39)
-
). It is necessary to set
fa54
Access
R
R
R
R
R
Access
W
W
W
W

Advertisement