Technical data

6 Technical data

6 .1 General

Gas type: natural gas, town gas, LPG (gaseous), flue
gas, biogas (max. 0.1 %-by-vol. H
Max. inlet pressure p
max.
page 22 (Adjusting range, switching hysteresis).
Electrical connection type: screw terminals.
Diaphragm pressure switch, silicone-free.
Diaphragm: NBR.
Housing: glass fibre reinforced PBT plastic with low gas
release.
Lower housing section: AlSi 12.
Enclosure: IP 65, safety class: 1.
Max. medium and ambient temperatures, see
page 21 (EU certified pressure switches) and
page 22 (UL, FM certified pressure switches).
Storage and transport temperature:
-20 to +40°C (-4 to +104°F).
Long-term use in the upper ambient temperature range
accelerates the ageing of the elastomer materials and
reduces the service life (please contact manufacturer).
The set switching point may palpably change in media
and ambient temperatures below -22°F (-30 °C).
C6097 · Edition 01.19
S) and air.
2
= withstand pressure, see
Recommended tightening torque:
Component
Cover screws
M16 x 1.5 cable gland
½" NPT conduit
Rp ⅛ pipe connection, aluminium
Rp ¼ (¼" NPT) gas connection
Rp ⅛ air connection, switch housing
Clamping terminal screws
T15 test point screw
Weight:
270 to 320 g (9.5 to 11.3 oz) depending on equipment.

6 .2 EU certified pressure switches

Max. test pressure for testing the entire system:
temporarily < 15 minutes 2 bar (29 psig).
Switching capacity:
U = 24 – 250 V AC,
I = 0.05 – 5 A at cos ϕ = 1,
I = 0.05 – 1 A at cos ϕ = 0.6.
Maximum medium and ambient temperatures:
-20 to +80°C (-4 to +176°F),
Line entrance:
M16 x 1.5 cable gland,
clamping range: diameters of 4 to 10 mm.
Cable diameter: AWG 24 to AWG 13,
0.5 to 1.8 mm (0.02 to 0.07").
Tightening torque [Ncm]
65
50
170 (15 lb")
250
1300
250
80
150
21