Honeywell C6097B Manual

Pressure switches

Advertisement

Quick Links

C6097A,B
Pressure Switches

APPLICATION

The C6097 Pressure Switches are safety devices used in
positive-pressure or differential-pressure systems to sense
gas or air pressure changes.

FEATURES

• For use with natural gas, liquid propane (LP) gas,
or air.
• Diaphragm-actuated safety-limit switch.
• Switch can be wired to turn on alarm.
• C6097A models break control circuit at setpoint
on pressure fall.
• C6097B models break control circuit at setpoint
on pressure rise.
• Lockout with manual reset and recycle options.
• Lockout models have external manual reset
button.
• Removable transparent cover protects scaleplate
and adjusting knob.
• Pipe tappings allow selection of positive
pressure, differential pressure (air only) or
venting connections (NPT mount only).
• 1/4 in. NPT or flange mount models for direct
mounting to Honeywell Integrated Valve Train.
• Optional switch position indicator lamp available.
• IP54 enclosure standard.
• Ranges: 0.4 to 5 in. wc, 3 to 21 in. wc,
12 to 60 in. wc or 1.5 to 7 psi.
• Surge orifice.
• Integral Vent Limiter.
Application ........................................................................
Features ...........................................................................
Specifications ...................................................................
Ordering Information ........................................................
Installation ........................................................................
Wiring ...............................................................................
Settings and Adjustments .................................................
Operation and Checkout ..................................................
PRODUCT DATA
Contents
1
1
2
2
4
4
6
6
7
65-0237-04

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell C6097B

  • Page 1: Table Of Contents

    • Switch can be wired to turn on alarm. • C6097A models break control circuit at setpoint on pressure fall. • C6097B models break control circuit at setpoint on pressure rise. • Lockout with manual reset and recycle options. • Lockout models have external manual reset button.
  • Page 2: Specifications

    If you have additional questions, need further information, or would like to comment on our products or services, please write or phone: 1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory). 2. Honeywell Customer Care...
  • Page 3 C6097A,B PRESSURE SWITCHES Table 1. Pressure Switch Model Selection. Manual Reset Non-Manual Reset Differential Differential Maximum Maximum Maximum Rated Operating Pressure Switch Pressure Minimum Maximum Differential (continuous) Manual Action at Model Range Setpoint Setpoint Nominal Maximum Type (psi) Reset Media Setpoint Comments C6097A1004...
  • Page 4: Installation

    C6097 models with flange mount can be fitted directly to 2 (52) TERMINAL DIAGRAM Honeywell Integrated Valve Train (model specific). See Fig. 2 and Table 1. The flange mount models vent internally, with no external tap. Mount the C6097A,B in any position.
  • Page 5 C6097A,B PRESSURE SWITCHES 3-11/32 (85) 1-19/32 (40) 4-1/8 (105) LAMP AND WIRES (13) 1/4 (6) SCREW CAPTIVE SCREW TERMINAL M16523 AND NUT PLATE C6097 COVER Fig. 3. 32003039-001 Position Indication Lamp Kit. Installation C6097 BODY WARNING SLIDE TWO LAMP WIRES THROUGH SLOT Explosion or Fire Hazard.
  • Page 6: Wiring

    (RM78XX) M16524 Fig. 5. Wiring the Position Indicator Lamp Kit in the C6097A. POSITION INDICATION LAMP FLAME C6097B SAFEGUARD CONTROL (RM78XX) M16525 Fig. 6. Wiring the Position Indicator Lamp Kit in the C6097B. Fig. 7. C6097 (manual reset switch model) with cover removed.
  • Page 7: Operation And Checkout

    Fig. 9. C6097 schematic. should open control circuit when pressure reaches cutoff point. For C6097B: Open the manual gas shutoff valve, wait a OPERATION AND CHECKOUT few minutes for the pressure to rise; then lower the scale setting until the switch breaks control circuit and locks out.
  • Page 8 C6097A,B PRESSURE SWITCHES Automation and Control Solutions Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Toronto, Ontario M1V 4Z9 customer.honeywell.com ® U.S. Registered Trademark © 2007 Honeywell International Inc. 65-0237—04 M.S. Rev. 09-07...