CD Automation MULTIDRIVE-1PH User Manual

Thyristor unit 850a

Advertisement

Quick Links

USER'S MANUAL
Rev. 09/2014
00003
CD Automation
Tel: +44 (0)1323 811-100
Email: info@cdautomation.co.uk
Web: www.cdautomation.co.uk/multidrive-1ph
MULTIDRIVE-1PH
Thyristor Unit
850A

Advertisement

Table of Contents
loading

Summary of Contents for CD Automation MULTIDRIVE-1PH

  • Page 1 MULTIDRIVE-1PH USER’S MANUAL Rev. 09/2014 Thyristor Unit 850A 00003 CD Automation Tel: +44 (0)1323 811-100 Email: info@cdautomation.co.uk Web: www.cdautomation.co.uk/multidrive-1ph...
  • Page 3: Table Of Contents

    SUMMARY 1 Important warnings for safety ..................5 2 Introduction ........................ 7 2.1 Advantages compared with analog thyristor unit 2.2 CD-KP 2.3 CD-EASY 2.4 Software Configurator 3 Quick Start ........................ 10 4 MULTIDRIVE Sizing....................11 5 Identification and Order Code ..................12 5.1 Identification of the unit 5.2 Order Code 6 Installation ........................
  • Page 4 10.3 Hardware Menu 10.4 Setup Menu 11 Firing type ....................... 36 11.1 Single Cycle (SC) 11.2 Burst Firing (BF ) 11.3 Phase Angle (PA ) 11.4 Delay Triggering (DT ) 11.5 Action of the Limit Current 11.6 Feed-back type 12 Connection description .................... 46 12.1 Access to the Electronic boards 12.2 Supply the Electronic Board PWI30 12.3 External Feed-Back...
  • Page 5: Important Warnings For Safety

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 1 Important warnings for safety This chapter contains important information for the safety. The not observance of these instructions may result in serious personal injury or death and can cause serious damages to the Thyristor unit and to the components system included.
  • Page 6 Caution: This icon is present in all the operational procedures where the Improper operation can cause damage for the Thyristor unit. CD Automation reserves the right to modify the own products and this manual without any advise.
  • Page 7: Introduction

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 2 Introduction A thyristor unit is semiconductor device which acts as a switch formed by two thyristors in ant parallel. To switch on the alternating current the input signal will be on and the thyristor will switch off at first Zero Crossing voltage with no input signal.
  • Page 8: Cd-Kp

    User’s Manual 2.2 CD-KP The CD-KP is designed to be connected with all CD Automation's Thyristor units via RS485 communication. On front unit is possible to read the principal operational parameters of the unit like: power, tension, current, reference, alarms, etc.
  • Page 9: Software Configurator

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 2.4 Software Configurator The software configuration is free and is possible download it from our site: www.cdautomation.com If the Order Code is in line with requirement, then MULTIDRIVE has been already configured in Factory and it's ready to use.
  • Page 10: Quick Start

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 3 Quick Start Caution: this procedure must be performed only by qualified persons. If the Order Code of the Thyristor unit is in line with what you really need, then MULTIDRIVE has been already configured in Factory and you just need to do the following steps: 1.
  • Page 11: Multidrive Sizing

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 4 MULTIDRIVE Sizing 4.1.1 Wiring with resistive load V = Nominal voltage phase to phase I = Nominal current to the load P = Nominal power to the load 4.1.2 Wiring with inductive load φ...
  • Page 12: Identification And Order Code

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 5 Identification and Order Code 5.1 Identification of the unit Caution: Before to install, make sure that the Thyristor unit have not damages. If the product has a fault, please contact the dealer from which you purchased the product.
  • Page 13: Order Code

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 5.2 Order Code...
  • Page 14: Installation

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 6 Installation Caution: Don't install near the hot elements or near the units that could give electromagnetic interferences. The MULTIDRIVE Thyristor unit must be always mounted in vertical position to improve air cooling on heat-sink.
  • Page 15: Dimensions

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 6.2 Dimensions MULTIDRIVE 1PH 850A (S14) Weight 22,5 kg 6.3 Fixing holes Size A(mm) B(mm) 850A (S14)
  • Page 16: Wiring Instructions

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 7 Wiring instructions Caution: this procedure must be performed only by qualified persons. The Thyristor unit could be susceptible to interferences lost by near equipments or by the power supply, for this reason in accord to the fundamental practices rules is opportune take some precautions: The electronic circuit of the Thyristor unit must be supplied from a dedicated voltage and not with •...
  • Page 17: Power Terminals

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 7.3 Power Terminals Warning: Before connecting or disconnecting the unit check that power and control cables are isolated from voltage sources. Terminal Description Line Input Phase Load Output Phase MULTIDRIVE 2PH 850A (S14)
  • Page 18: Command Terminals

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 7.4 Command Terminals FANS and SYNK Terminal Terminal Description Earth Earth Phase L2 230V Voltage Supply for Electronic Boards 230V Voltage Supply for Electronic Boards Terminal Description Isolated output +24Vdc MAX 20mA GND for Digital Input...
  • Page 19: Diagram Of Control Connection

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 7.5 Diagram of control connection Caution: this procedure must be performed only by qualified persons. NOTE: * The user installation must be protecting by electromagnetic circuit breaker or by fuse isolator. • *² Use an appropriate external transformer based on the voltage supply of the electronic board •...
  • Page 20: Power Output Features

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 8 Power output features Voltage Repetitive peak Latching Max peak Leakage T value Frequency Isolation Current Power loss range reverse voltage current one cycle current range Voltage (10msec.) (480V) (600V) (mAeff) (mAeff) tp=10msec...
  • Page 21: Led Status And Alarms

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 9 Led status and Alarms 9.1 LED Status Table On the DDC30 Electronic board there are two LED that indicates the state of the Electronic cards: STATUS DESCRIPTION For All size The power supply is not connected or fault on the electronic board...
  • Page 22: Critical Alarms

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 9.2 Critical Alarms When a critical alarm is active, it stops the MULTIDRIVE thyristor unit and activates the relative digital output (terminal 11). The parameter P001  allows to visualize the state of these alarms (see par. Errore. L'origine riferimento non è...
  • Page 23: Not Critical Alarm

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 9.3 Not Critical Alarm The Not Critical Alarm, doesn’t stop the MULTIDRIVE thyristor unit, but is possible to associate an digital output at these alarms (see par. 12.7). The parameter P002  allows to visualize the state of these alarms 9.3.1 SCR Short Circuit...
  • Page 24: Control Panel

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 10 Control Panel The Configuration Parameters are accessible from the Control Panel, from the software configurator or through the serial communication port RS485. RS485 Communication is available on separated and dedicated manual. The Control Panel is placed on the front of the thyristor unit, on his display you can visualize the alarms,...
  • Page 25: Scroll The Parameters

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 10.1 Scroll the parameters...
  • Page 26: Operator Menu

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 10.2 Operator Menu Code of Critical alarm: This parameter read only gives information on the following alarms that they stop the MULTIDRIVE. Default Parameter Parameter Par. Contents Value Value Value Value Value Display...
  • Page 27 CD Automation srl MULTIDRIVE-1PH 850A User’s Manual Default Parameter Parameter Par. Contents Value Value Value Value Value Display Name Type Setpoint Digital  L_SP 4095 100,0 Value Remote Set-point value: This parameter read only contains the analog setpoint value present at the terminals 17-18 of the command terminals.
  • Page 28 CD Automation srl MULTIDRIVE-1PH 850A User’s Manual Voltage Output: This parameter read only show the voltage output . Default Parameter Parameter Par. Contents Value Value Value Value Value Display Name Type  Vout Voltage Output − 1000 1000 Power Output: This parameter read only show the power output .
  • Page 29: Hardware Menu

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 10.3 Hardware Menu Calibration MIN value of analog input 1: This parameter saves in memory the min value of the primary analog input. Default Parameter Parameter Par. Contents Value Value Value Value Value...
  • Page 30 CD Automation srl MULTIDRIVE-1PH 850A User’s Manual Calibration MAX value of analog input 2: This parameter saves in memory the Max value of the secondary analog input. Default Parameter Parameter Par. Contents Value Value Value Value Value Display Name Type Save value ...
  • Page 31 CD Automation srl MULTIDRIVE-1PH 850A User’s Manual Offset of the Analog Outputs: This parameter is used to set the offset for the Analog Outputs. Default Parameter Parameter Par. Contents Value Value Value Value Value Display Name Type Analogue Output ...
  • Page 32 CD Automation srl MULTIDRIVE-1PH 850A User’s Manual Full scale of Analog Output 3 (RMS Current): This parameter is used to adjust the full scale value of the analog output. Default Parameter Parameter Par. Contents Value Value Value Value Value Display...
  • Page 33 CD Automation srl MULTIDRIVE-1PH 850A User’s Manual Baud Rate: This parameter selects the Baud rate on the serial port. Default Parameter Parameter Par. Contents Value Value Value Value Value Display Name Type Baud Rate on  bAud serial port Sample Values and Note ...
  • Page 34: Setup Menu

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 10.4 Setup Menu Firing mode Selection: This parameter selects the Firing Type. Default Parameter Parameter Par. Contents Value Value Value Value Value Display Name Type Firing mode  Selection * if not specified in the Order Code Sample Values and Note ...
  • Page 35 CD Automation srl MULTIDRIVE-1PH 850A User’s Manual Burst Firing Setting: It defines the number of voltage cycles in ON condition at 50% of power demand. Default Parameter Parameter Par. Contents Value Value Value Value Value Display Name Type Burst Firing ...
  • Page 36: Firing Type

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 11 Firing type Choose an correct firing type allows to optimize the thyristor unit for the installed load. The firing type has already configured in line with customer requirements that are defined in the Order Code.
  • Page 37 CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 11.1.1 Suggested recipe for Single Cycle The firing type has already configured in line with customer requirements that are defined in the Order Code. The Order Code is written on the identification label.
  • Page 38: Burst Firing (Bf )

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 11.2 Burst Firing (BF  The Burst Firing is similar to the Single Cycle, but consecutive cycles ON are selectable between 2 and 255, with input signal equal at 50%. Burst Firing is a method zero crossing that it reduces the electromagnetic interferences because the thyristor switches at zero voltage crossing.
  • Page 39 CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 11.2.2 Suggested recipe for Burst Firing The firing type has already configured in line with customer requirements that are defined in the Order Code. The Order Code is written on the identification label.
  • Page 40: Phase Angle (Pa )

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 11.3 Phase Angle (PA  The Phase Angle firing allow the control of the power on the load, for this firing the thyristor can be in conduction only for a part of the voltage cycle.
  • Page 41 CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 11.3.2 Suggested recipe for Phase Angle The firing type has already configured in line with customer requirements that are defined in the Order Code. The Order Code is written on the identification label.
  • Page 42: Delay Triggering (Dt )

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 11.4 Delay Triggering (DT  The Delay Triggering firing is used the control a primary of transformer coupled with the normal resistances on the secondary (N.B. don't connect cold resistances on the secondary like: Superkanthal, Molybdenum, Platinum, Tungsten, Quartz Lamp).
  • Page 43 CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 11.4.1 Suggested recipe for Delay Triggering The firing type has already configured in line with customer requirements that are defined in the Order Code. The Order Code is written on the identification label.
  • Page 44: Action Of The Limit Current

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 11.5 Action of the Limit Current The Current Limit is available for each firing type. It control the firing angle of the thyristor to maintain the three RMS current under the set value.
  • Page 45: Feed-Back Type

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 11.6 Feed-back type The Feed-back type has already configured in line with customer requirements that are defined in the Order Code. The Order Code is written on the identification label. However, if you wish to change the Feed-back type you can use the software configurator or the Control Panel (see par.
  • Page 46: Connection Description

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 12 Connection description 12.1 Access to the Electronic boards To have access to the electronic boards the user must removing the unit’s cover (see par.7.1) Warning: Before operate, be sure that power and control cables are isolated from voltage...
  • Page 47: Supply The Electronic Board Pwi30

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 12.2 Supply the Electronic Board PWI30 The MULTIDRIVE thyristor unit, to work, requires a voltage supply for the electronic boards. This voltage is used also to supply the internal fans. The consumption is 20VA max, at this you must add the consumption of the internal fans (see par. 8.2).
  • Page 48: Analog Inputs

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 12.4 Analog Inputs The MULTIDRIVE thyristor unit has 3 configurable analog inputs (0÷10V, 4÷20mA, ecc): The primary input for the analog setpoint, the secondary input for the setpoint correction and the External Current Profiler for the current limit.
  • Page 49 CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 12.4.2 Secondary Input (Terminals 19 and 20 - see par. 7.4) The secondary input for the setpoint correction is already configured in line with customer requirements that are defined in the Order Code. The Order Code is written on the identification label.
  • Page 50: Analog Outputs

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 12.5 Analog Outputs The MULTIDRIVE thyristor unit has 4 configurable analog outputs (0÷10V, 4÷20mA, ecc). The output 1 is for retransmitting the average power on the three phases, and the others 3 is for the retransmitting the RMS current on the phases L1, L2 and L3 12.5.1 Output 1: Average Power (Terminals 15 and 23 or 16 and 23 - see par.
  • Page 51 CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 12.5.2 Output 2: Voltage Output (Terminals 15 and 24 or 16 and 24 - see par. 7.4) The Voltage output is already configured in line with customer requirements that are defined in the Order Code.
  • Page 52: Digital Input

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 12.6 Digital Input The MULTIDRIVE thyristor unit has 6 digital inputs opto-isolated to 24Vdc. You can activate the inputs with the internal supply (see par. 7.5) or with an external source for example the PLC.
  • Page 53: Digital Output

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 12.7 Digital Output The MULTIDRIVE thyristor unit has 4 digital output with relay contact (Max 500mA, 125Vac), an output control the main contactor and is a normally open (NO) fixed contact, and the others output gives indications of the alarms state, the contacts can be (NO or NC).
  • Page 54 CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 12.7.3 Configurable Digital Output 2 (Terminals 12 and 14 see par. 7.4) This digital output can be configured in order to activate itself after that one of these alarms occors: SCR in short circuit •...
  • Page 55 CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 12.7.4 Configurable Digital Output 3 (Terminals 13 and 14 see par. 7.4) This digital output can be configured in order to activate itself after that one of these alarms occors: SCR in short circuit •...
  • Page 56: Pg Connector

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 12.8 PG Connector The PG Connector is used to configure the thyristor unit with the configuration software and with the programming cable. The programming cable is not included. PG Connector...
  • Page 57: Rs485 Serial Port

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 12.9 RS485 Serial Port The serial communication port RS485 is available on the Command Terminals and on the 9pin DIN male connector. On this port may be done a network up to 127 MULTIDRIVE.
  • Page 58: Internal Fuse

    CD Automation srl MULTIDRIVE-1PH 850A User’s Manual 13 Internal Fuse The MULTIDRIVE thyristor unit have internal fuse extrarapid at low I²t for the thyristor protection of against the short-circuits. The fuse must have I²t lower than the thyristor one (I²t max) Caution: USE ONLY EXTRARAPID FUSE WITH APPROPRIATE I²...
  • Page 59: Maintenance

    • 14.4 Warranty condition CD Automation gives a 12 months warranty to its products. The warranty is limited to repairing and parts substitution in our factory and does exclude products not properly used and fuses. Warranty does not include products with serial numbers deleted. The faulty product should be shipped to CD Automation at customer’s cost and our Service will evaluate if product is under warranty terms.
  • Page 60 CD Automation srl MULTIDRIVE-1PH 850A User’s Manual ENG MULTIDRIVE-1PH_850A...