Honeywell CentraLine LYNX BACnet CLLYUB1012S Product Data page 9

Programmable vav/unitary controllers

Advertisement

Table 4. Description of wiring terminals (CLLYUB6438S,
CLLYVB6436AS, and CLLYVB6438S)
TERMINAL
LABEL
INPUT POWER & GROUND
1
24 VAC
24 VAC POWER
(A
2
24 VAC COM
24 VAC POWER
(A
3
EGND
EARTH GROUND
4
SHLD
SHIELD
5
SBUS 1
SYLK
6
SBUS 2
SYLK
NETWORK CONNECTIONS
7
BAC+
BACnet COMMUNICATIONS
8
BAC-
BACnet COMMUNICATIONS
DIGITAL OUTPUTS
9
DO-1
DIGITAL OUTPUT
10
DO-2
DIGITAL OUTPUT
11
COM
COMMON
12
DO-3
DIGITAL OUTPUT
13
DO-4
DIGITAL OUTPUT
14
COM
COMMON
15
DO-5
DIGITAL OUTPUT
16
DO-6
DIGITAL OUTPUT
17
COM
COMMON
(B
18
DO-7
DIGITAL OUTPUT
(B
19
DO-8
DIGITAL OUTPUT
(B
20
COM
COMMON
ANALOG OUTPUTS
21
AO-1
ANALOG OUTPUT
22
COM
COMMON
23
AO-2
ANALOG OUTPUT
24
AO-3
ANALOG OUTPUT
25
COM
COMMON
DIGITAL INPUTS
26
DI-1
DIGITAL INPUT
27
DI-2
DIGITAL INPUT
28
COM
COMMON
29
DI-3
DIGITAL INPUT
30
DI-4
DIGITAL INPUT
ATTACHED DEVICE(S) POWER
31
20 VDC
20 VDC POWER
UNIVERSAL INPUTS
32
UI-1*
UNIVERSAL INPUT
33
COM
COMMON
34
UI-2
UNIVERSAL INPUT
35
UI-3
UNIVERSAL INPUT
36
COM
COMMON
37
UI-4
UNIVERSAL INPUT
38
UI-5
UNIVERSAL INPUT
39
COM
COMMON
40
UI-6
UNIVERSAL INPUT
(A
A jumper should be installed between 24 VAC COM (term. 2) and EGND
(term. 3). Further, EGND (term. 3) should be connected to a verified earth
ground.
(B
In the case of the CLLYVL6436AS controller, only, terminals 18, 19, and 20
(DO-7, DO-8, and COM) are not present. The actuator is internally hardwired to
these terminals.
(C
Analog outputs may be configured as digital outputs and operate as follows:
FALSE (0%) -> 0 Vdc (0 mA), TRUE (100%) -> the max. 11 Vdc (22 mA)
(D
Digital inputs: open circuit = FALSE, closed circuit = TRUE
*UI-1 is selectable as a fast digital pulse meter.
LYNX BACnet PROGRAMMABLE, VAV/UNITARY CONTROLLERS – PRODUCT DATA
CONNECTION
(C
(D
Table 5. Description of wiring terminals (CLLYVB0000AS,
CLLYVB4022AS, and CLLYVB6436AS)
TERMINAL
LABEL
INPUT POWER & GROUND
1
24 VAC
(A
2
24 VAC COM
(A
3
EGND
4
20VDC
5
SBUS 1
6
SBUS 2
NETWORK CONNECTIONS
7
BAC+
8
BAC-
9
SHIELD
DIGITAL OUTPUTS
10
DO-3
11
COM
12
DO-4
13
DO-2
14
COM
15
DO-1
ANALOG OUTPUTS
16
AO-2
17
COM
18
AO-1
UNIVERSAL INPUTS
19
UI-4
20
COM
21
UI-3
22
UI-2
23
COM
*
24
UI-1
(A
A jumper should be installed between 24 VAC COM (term. 2) and
EGND (term. 3). Further, EGND (term. 3) should be connected to a
verified earth ground.
*
UI-1 is selectable as a fast digital pulse meter.
MS/TP MAC Address DIP Switches
The MS/TP MAC address DIP switches are used to set the
unit's MAC address. Each LYNX controller on an MS/TP net-
work must have a unique MAC address in the range of 0-127
(address 0 should be avoided as it is the Honeywell factory
default MAC address for all MS/TP devices).
MS/TP Service Connector Pins
Local device MS/TP network connection is provided via the
molex connector pins.
9
CONNECTION
24 VAC POWER
24 VAC POWER
EARTH GROUND
20 VDC
SYLK
SYLK
BACnet COMMUNICATIONS
BACnet COMMUNICATIONS
SHIELD
DIGITAL OUTPUT
COMMON
DIGITAL OUTPUT
DIGITAL OUTPUT
COMMON
DIGITAL OUTPUT
ANALOG OUTPUT
COMMON
ANALOG OUTPUT
UNIVERSAL INPUT
COMMON
UNIVERSAL INPUT
UNIVERSAL INPUT
COMMON
UNIVERSAL INPUT
EN0Z-0959GE51 R0615