Honeywell CentraLine LYNX BACnet CLLYUB1012S Product Data page 13

Programmable vav/unitary controllers

Advertisement

2- OR 3-WAY CHILLER
2- OR 3-WAY HOTWATER/
WATER VALVE
STEAM VALVE
SERIES 70
SERIES 70
VALVE ACTUATOR
VALVE ACTUATOR
2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 4
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
CLLYUB6438S
1 2 3 4 5 6 7 8
24VAC
BACnet MS/TP-
BACnet MS/TP+
24VAC
COM
1
2
SHIELD
Fig. 18. Controller wiring diagram (CLLYUB6438S shown)
with 4...20 mA heating, cooling, and ML6161 damper
actuator
NOTE 1: Earth ground wire length should be held to a
minimum. Use the heaviest gauge wire available,
up to 14 AWG (2.0 mm
2
AWG (1.0 mm
), for earth ground wire.
NOTE 2: Ensure that all transformer / power wiring is as
shown. Reversing terminations will result in
equipment malfunction.
LYNX BACnet PROGRAMMABLE, VAV/UNITARY CONTROLLERS – PRODUCT DATA
7
CLCM4T111
6
WALL MODULE
5
LED
4
BYPASS
3
SET-POINT
2
SENSOR
1
GND
DISCHARGE
AIR TEMP.
1
1 1 1 1 1 1 1 1 1 2
2 3 4 5 6 7 8 9 0
9
0
1
DAMPER CLOSE
CCW
COM
DAMPER
DAMPER OPEN
ACTUATOR
CW
2
), with a minimum of 18
CLLYUB6438S
1 2 3 4 5 6 7 8
24VAC
24VAC
COM
FAN
RP7517B
BROWN
BLACK
Fig. 19. Controller wiring diagram (CLLYUB6438S shown)
for RP7517B pneumatic transducer
NOTE 1: Use 6 mm tubing. Minimum branch line must be
1.8 m or longer.
ML6161
NOTE 2: Terminals 21, 23, and 24 are analog outputs.
13
2
2 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 4
1 2 3 4 5 6 7 8 9 0 1 2 3 4 5 6 7 8 9 0
1
1 1 1 1 1 1 1 1 1 2
9
0
1
2 3 4 5 6 7 8 9 0
1
2B
PNEUMATIC
VALVE
ACTUATOR
1M
M
BLUE
EN0Z-0959GE51 R0615