Type OS2 Slam-Shut Device
WARNING
!
Failure to follow these instructions or to
properly install and maintain this equipment
could result in an explosion and/or fire
causing property damage and personal injury
or death.
Fisher™ slam-shut devices must be installed,
operated and maintained in accordance
with federal, state and local codes, rules
and regulations and Emerson Process
Management Regulator Technologies,
Inc. instructions.
If the slam-shut device vents gas or a leak
develops in the system, service to the unit
may be required. Failure to correct trouble
could result in a hazardous condition.
Call a gas service person to service the
unit. Only a qualified person must install or
service the slam-shut devices.
Introduction
Scope of the Manual
This instruction manual provides installation, maintenance
and parts ordering information for the Types OS2 and
OSD2 slam-shut devices for the Types OSE, 627-OSX,
EZH-OSX, EZHSO-OSX, EZL-OSX and EZR-OSX. For
further instructions on the Types 627, EZH, EZHSO, EZL
or EZR refer to the corresponding instruction manual of
these products.
Description
Slam-shut devices are used to totally and rapidly cut off
gas flow when the inlet and/or outlet pressure in the system
either exceeds or drops below the setpoints. The Types OS2
and OSD2 slam-shut devices consist of a valve, mechanism
box (BM1 or BM2) and either one or two modular sensing
elements called manometric devices (Type BMS1 or BMS2)
(see Figure 2).
TYPE E
VALVE
BODY
W8133
TYPE OSE STAND-ALONE SLAMSHUT
TYPE EZR
REGULATOR
W8136
TYPE EZR-OSX
Figure 1. Type OS2 Slam-Shut Device on
Types OSE and EZR-OSX Constructions
Type OS2
TYPE OS2
SLAM-SHUT
DEVICE
TYPE OS2
SLAM-SHUT
DEVICE

Advertisement

Table of Contents
loading

Summary of Contents for Emerson Fisher OS2

  • Page 1 Fisher™ slam-shut devices must be installed, operated and maintained in accordance with federal, state and local codes, rules and regulations and Emerson Process Management Regulator Technologies, Inc. instructions. TYPE E If the slam-shut device vents gas or a leak...
  • Page 2: Specifications

    Type OS2 Specifications This section lists the specifications for the Type OS2 slam-shut valve. Factory specifications are stamped on the nameplate fastened on the valve at the factory. Body Sizes and End Connection Styles Maximum Set Pressure Type OSE 1470 psig / 101 bar or maximum body rating, whichever is lower WCC Steel 1 and 2 NPT;...
  • Page 3 Type OS2 TYPE BMS2 (LEFT SIDE) TYPE BMS1 TYPE OS2 TYPE BMS1 (RIGHT SIDE) E0564 E0565 MECHANISM BOX (BM1) WITH 1 MANOMETRIC SENSING DEVICE MECHANISM BOX (BM2) WITH 2 MANOMETRIC SENSING DEVICES (TYPE BMS1) (TYPES BMS1 AND BMS2) TOP-MOUNTED (STAND-ALONE TYPE OSE VALVE) Figure 2.
  • Page 4 Type OS2 TYPE PRX TYPE SA/2 EQUALIZER BYPASS MANOMETRIC DEVICE STEM 8 TO 10 PIPE DIAMETERS MANOMETRIC DEVICE VALVE PLUG COURSE CLAPET MECHANISM E0939 INLET PRESSURE OUTLET PRESSURE EVENT PIN D1 ATMOSPHERIC PRESSURE PIN D2 LOADING PRESSURE PILOT SUPPLY PRESSURE TYPE EZH OSX MANOMETRIC DEVICE STEM MANOMETRIC DEVICE...
  • Page 5: Installation

    Type OS2 Table 2. Spring Ranges, Part Numbers and Maximum and Minimum Pressures for the Manometric Sensing Devices (Types BMS1 and BMS2) MAXIMUM DIFFERENCE MAXIMUM RECOMMENDED MANOMETRIC MANOMETRIC BETWEEN SPRING SPRING PART SENSING INLET SETPOINT SPRING RANGE SENSING SENSING OVERPRESSURE AND COLOR NUMBER PRESSURE,...
  • Page 6 Type OS2 DOWNSTREAM SENSING LINE DOWNSTREAM SENSING LINE UPSTREAM BLOCK VALVE OPTIONAL STRAINER OPTIONAL STRAINER UPSTREAM BLOCK BLOCK BLOCK VALVE VALVE VALVE TYPE OSE SLAM-SHUT VALVE TYPE OSE PRESSURE PRESSURE SLAM-SHUT VALVE REGULATOR REGULATOR E0560 E0561 OVERPRESSURE AND UNDERPRESSURE SHUTOFF MINIMUM/MAXIMUM UPSTREAM AND USING ONE MANOMETRIC DEVICE DOWNSTREAM PRESSURE...
  • Page 7 Type OS2 Type BMS1 (Figure 5) ADJUSTING SCREW LOCKNUT TRIPPING HOOK Overpressure Shutoff Only PIN D2 THREADED STEM TRIPPING Adjusting the Threaded Stem: PLATE 1. Remove the tripping hook or rotate so it cannot contact PIN D1 Pin D2. TRIPPING HOOK 2.
  • Page 8 Type OS2 Type BMS2 (Figure 6) PUSH BUTTON LOCKNUT ADJUSTING SCREW PUSH BUTTON Overpressure Shutoff Only PIN D2 THREADED TRIPPING STEM Adjusting the Overpressure Push Button: PLATE 1. Remove the tripping hook. CAUTION PIN D1 TRIPPING THREADED Be sure there is no pressure in the HOOK ADJUSTING SCREW STEM...
  • Page 9 Type OS2 RESET PIN WITH WHITE DOT SECOND STAGE RELEASING SHAFT TRAVEL STOP SLIDING TRAVEL STOP CLEVIS VALVE OPEN VALVE CLOSED E0611 E0612 SLAM-SHUT VALVE OPEN SLAM-SHUT VALVE CLOSED RESETTING TOOL STEP A TRAVEL STOP TRAVEL STOP STEP B VALVE OPEN VALVE CLOSED E0613 E0614...
  • Page 10: Maintenance

    Type OS2 Shutdown* Note Because the Type OS2 mounted on the WARNING Types 627-OSX, EZH-OSX, EZL-OSX and EZR-OSX is turned 180°, the following directions apply to the Type OSE only, To avoid personal injury or property damage however, the reset procedure for the due to explosion or damage to shutoff Types 627-OSX, EZH-OSX, EZL-OSX device, regulator or downstream components...
  • Page 11 Type OS2 LOCATION FOR SWITCH (KEY 27) RESET PIN WITH WHITE DOT MECHANISM BOX (KEY 16A) TRIPPING PLATE (KEY 16B) MANOMETRIC SENSING DEVICE (TYPE BMS1, KEY 17) CLIP MANOMETRIC DEVICE THREADED STEM SLIDING CLEVIS (KEY 16F) SECOND STAGE RELEASING SHAFT (KEY 16D) TRAVEL STOP RESETTING TOOL STEM...
  • Page 12 Type OS2 COUPLING HEAD COUPLING (KEY 5L) (KEY 5M) HOLES FOR SPANNER COUPLING WRENCH HEAD (KEY 5M) VALVE PLUG (KEY 5H) EQUALIZER BYPASS (KEY 5A) ROLL PINS EQUALIZER (KEY 5K) BYPASS (KEY 5A) PLUG O-RING VALVE PLUG DISK (KEY 5J) (KEY 5N) W6855 W6853_1...
  • Page 13 Type OS2 TYPE BMS MANOMETRIC DEVICE (KEY 17) TYPE BMS1 BRACKET KIT (KEY 25) TYPE BMS2 BRACKET KIT (KEY 26) DIAPHRAGM, PISTON, BELLOWS, TYPES 162 AND 71 TYPES 27 AND 17 TYPES 236 AND 315 Figure 11. Manometric Sensing Device Types 4.
  • Page 14: Parts Ordering

    Type OS2 Parts List 5. Inspect the rubber joint gasket (key 38C) for deterioration or damage and replace if necessary. Description Part Number 6. Loosen the adjustment locknut on the adjusting screw. Then unscrew and remove the adjusting screw. Parts kit (includes keys 5J, 7, 10 and 11) NPS 1 / DN 25 FA197123X12 7.
  • Page 15 Type OS2 Description Part Number Description Part Number Valve Body Assembly (continued) Roll pin (2 required) (For NPS 1 through 6 / DN 25 through 150 only) NPS 1 through 6 / DN 25 through 150 FA405635T12 (Body, Seat ring and Seat O-ring) (continued) Coupling Types EZHOSX, EZROSX and EZLOSX (X-Body) NPS 1 / DN 25...
  • Page 16 Type OS2 Description Part Number Description Part Number Mechanism Box (BM) Cap Screw NPS 1 / DN 25 (4 required) 1R281124052 For NPS 1 through 6 / DN 25 through 150 FA181067T12 NPS 2 / DN 50 (8 required) 1A453324052 For NPS 8 and 10 / DN 200 and 250 FA181166X12 NPS 3 / DN 80 (8 required)
  • Page 17 Type OS2 DETAIL OF DETAIL OF NPS 2 AND 3 / NPS 1 / DN 25 DN 50 AND 80 E0603 E0602 VALVE PLUG VALVE PLUG SHOWN SHOWN DETAIL AREA OPEN CLOSED E0601 NPS 4 AND 6 / DN 100 AND 150 Figure 12.
  • Page 18 Type OS2 DETAIL OF NPS 10 / DN 250 Figure 13. Type OSE Slam-Shut Valve Assembly for NPS 8 and 10 / DN 200 and 250...
  • Page 19 Type OS2 LOCATION OF CONTACT SWITCH WIRING KEY 27 NF—NORMALLY CLOSED NO—NORMALLY OPEN NF—BK/BU E0615 NO—BK/BN Figure 14. Optional Contact Limit Switch Table 3. Optional Contact Limit Switch C1 CONTACT VERSION—EXPLOSION PROOF CONNECTION WITH CABLE AND TIGHT-SHUT PACKING GLAND Maximum Current 7.0A 0.8A Maximum Voltage...
  • Page 20 Technologies, Inc. All rights reserved. 06/19. Emerson Automation Solutions The Emerson logo is a trademark and service mark of Emerson Electric Co. All other marks are the property of their prospective owners. Fisher™ is a mark owned by Fisher Controls International LLC, a...