ABB Relion SMU615 Product Manual page 16

Substation merging unit
Hide thumbs Also See for Relion SMU615:
Table of Contents

Advertisement

Substation Merging Unit
SMU615
Product version: 1.0
Table 19. Electromagnetic compatibility tests, continued
Description
Emission tests
• Conducted
0.15...0.50 MHz
0.5...30 MHz
• Radiated
30...230 MHz
230...1000 MHz
1...3 GHz
3...6 GHz
Table 20. Insulation tests
Description
Dielectric tests
Impulse voltage test
Insulation resistance measurements
Table 21. Mechanical tests
Description
Vibration tests (sinusoidal)
Shock and bump test
Table 22. Environmental tests
Description
Dry heat test
Dry cold test
Damp heat test
Change of temperature test
16
Type test value
<79 dB (µV) quasi peak
<66 dB (µV) average
<73 dB (µV) quasi peak
<60 dB (µV) average
<40 dB (µV/m) quasi peak, measured at 10m
distance
<47 dB (µV/m) quasi peak, measured at 10m
distance
<76 dB (µV/m) peak
<56 dB (µV/m) average, measured at 3m
distance
<80 dB (µV/m) peak
<60 dB (µV/m) average, measured at 3m
distance
Type test value
2 kV, 50 Hz, 1 min
500 V, 50 Hz, 1 min, communication
5 kV, 1.2/50 μs, 0.5 J
1 kV, 1.2/50 μs, 0.5 J, communication
>100 MΩ, 500 V DC
Reference
IEC 60068-2-6 (test Fc)
IEC 60255-21-1: 1988
IEC 60068-2-27 (test Ea shock)
IEC 60068-2-29 (test Eb bump)
IEC 60255-21-2: 1988
Type test value
• 96 h at +55ºC
• 16 h at +85ºC
• 96 h at -25ºC
• 16 h at -40ºC
• 6 cycles (12 h + 12 h) at +25°C...+55°C,
humidity >93%
• 5 cycles (3 h + 3 h) at -25°C...+55°C
1MRS758420 B
Reference
IEC 60255-26:2013
CISPR 11:2009+A1:2010
CISPR 22:2008
GB 14598.26-2015
Reference
IEC 60255-272013
IEC 60255-272013
IEC 60255-272013
Requirement
Class 2
Class 2
Reference
IEC 60068-2-2:2007
IEC 60068-2-1:2007
IEC 60068-2-30:2005
IEC 60068-2-14:2009
ABB

Advertisement

Table of Contents
loading