Table 19. Electromagnetic compatibility tests
Description
Slow damped oscillatory wave immunity test
• Common mode
• Differential mode
Electrostatic discharge test
• Contact discharge
• Air discharge
Conducted immunity test
Radiated electromagnetic field immunity test
Electrical fast transient/burst immunity test
Surge immunity test
• Communication
• Other ports
Power frequency magnetic field immunity test
• Continuous
• 1...3 s
Pulse magnetic field immunity test
Damped oscillatory magnetic field immunity test
• 2 s
• 1 MHz
A.C. and D.C. voltage dips and interruptions
test
Power frequency immunity test
• Common mode
• Differential mode
ABB
Type test value
2.5 kV
2.5 kV
8 kV
15 kV
10 V (rms)
f = 150 kHz...80 MHz
20 V/m (rms)
f = 80 MHz...1 GHz; 1.4...2.7 GHz
4 kV
0.5 kV, line-to-earth
1 kV, line-to-earth
2 kV, line-to-earth
0.5 kV, line-to-earth
1 kV, line-to-earth
2 kV, line-to-earth
0.5 kV, line-to-line
1 kV, line-to-line
300 A/m
1000 A/m
1000 A/m
6.4/16 µs
100 A/m
400 transients/s
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
Binary inputs only
300 V rms
150 V rms
1MRS758420 B
Reference
IEC 60255-26:2013
IEC 61000-4-18:2006+A1:2010
ANSI/IEEE C37.90.1-2012
GB 14598.26-2015
IEC 60255-26:2013
IEC 61000-4-2:2008
GB 14598.26-2015
IEC 60255-26:2013
IEC 61000-4-6:2008
GB 14598.26-2015
IEC 60255-26:2013
IEC 61000-4-3:2006
ANSI/IEEE C37.90.2-2004
GB 14598.26-2015
IEC 60255-26:2013
IEC 61000-4-4:2012
ANSI/IEEE C37.90.1-2012
GB 14598.26-2015
IEC 60255-26:2013
IEC 61000-4-5:2005
GB 14598.26-2015
IEC 60255-26:2013
IEC 61000-4-8:2009
GB 14598.26-2015
IEC 61000-4-9:2001
GB 14598.26-2015
IEC 61000-4-10:2001
GB 14598.26-2015
IEC 60255-26:2013
IEC 61000-4-11:2004
IEC 61000-4-29:2000
GB 14598.26-2015
IEC 60255-26:2013
IEC 61000-4-16:1998+A2:2009
GB 14598.26-2015
15