Service level menu (for qualified heating engineers only)
7

7.5.20 Daily heating time

Menu: Service > Settings > Daily heating time
This setting determines the start time for daily heating. Daily heating runs for a maximum of 3 hours.
Warning: Risk of scalding due to water temperatures over 60 °C!
V Only schedule daily heating for periods outside normal usage times.
V Inform the occupants of the premises of the times for daily heating.
Setting range
00:00 h - 23:59 h
Tab. 33

7.5.21 Daily heating target temperature

Menu: Service > Settings > Daily heating target temperature
This setting determines the temperature for daily heating.
Setting range
60 - 70 °C
Tab. 34
64
Default setting
00:00 h
Default setting
60 °C
Logamatic SC40 - Technical specifications are subject to change without prior notice.