Download Print this page

Specifications - Honeywell V5197A1011 Product Data

Firing rate gas valve

Advertisement

V5197A FIRING RATE GAS VALVE

SPECIFICATIONS

IMPORTANT
The specifications in this publication do not
include normal manufacturing tolerances; therefore,
an individual unit may not exactly match the
specifications listed. Also, this product is tested
and calibrated under closely controlled conditions,
and some minor differences in performance can be
expected if those conditions are changed.
Models:
V5197A1003: Small body.
V5197A1011: Large body.
Type of Gas: Air, natural, manufactured, mixed or liquefied
petroleum (LP) gases only.
Pipe Size of the gas train: 3/4 in. (19 mm), 1 in. (25 mm),
1-1/4 in. (32 mm), 1-1/2 in. (38 mm), 2 in. (51 mm),
2-1/2 in. (64 mm), 3 in. (76 mm).
Pressure Rating: Maximum operating pressure of 15 psi
(1 Bar).
Maximum Valve Capacities: SCFH gas: 0.64 sp. gr. at
1 in. wc pressure drop across valve (flow limit adjustment
set at 100% open). See Table 1.
Table 1. Maximum Flow Capacity
(natural gas at 0.64 sp.gr.) at 1 in. w.c. (2.5 mBar)
Pressure Drop Across Valve.
Pipe Size in in. (mm)
3/4 (19)
2450
1 (25)
3080
1-1/4 (32)
4430
1-1/2 (38)
5010
2 (51)—small body
5480
2 (51)—large body
12,600
2-1/2 (64)
14,800
3 (76)
16,900
a
Standard cubic feet per hour (SCFH) and standard cubic
meters per hour (SCMH) listed. For other gases, multiply the
listed capacity by the square root of (0.64 divided by the
specific gravity of the other gas).
Flow curves: See Fig. 1 through 8.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
65-0247—2
a
Flow Capacity
SCFH
SCMH
69
87
125
142
155
356
419
478
NOTE: The percentage settings listed on the figures refer
to the setting of the flow adjustment screw on the
bottom of the V5197. Pressure drops are shown as
solid, broken or dotted lines on the figures.
Bolt/Nut Fasteners (Provided with the valve):
Small body: 3/8-16 by 1-3/8, Grade 5 bolt. Metric equivalent
M8x1.25x35mm, class 9.8. Tighten to 13 ft-lb (18 N•m).
Large body: 1/2-13 by 2.00, Grade 5 bolt. Metric equivalent
M12x1.75x50mm, class 9.8. Tighten to 25 ft-lb
(34 N•m).
Tapping and plug: Two downstream 1/4 in. NPT taps.
Plugs : 1/4 in. hex socket.
Ambient Operating Temperature Rating: -40°F to +150°F
(-40°C to +66°C).
Material: Cast aluminum body, brass and stainless steel
internal parts, NBR seals.
Mounting: Directly bolted to Integrated Valve Train (IVT)
components or IVT adapters.
Mechanical Strength: Group 2.
Maximum flow adjustment (Fig 9):
Located on the bottom of the valve with a 1/4 in. (6 mm)
hex key:
To decrease the maximum flow, turn clockwise
to increase the maximum flow, turn
counterclockwise
Mounting position: Any position.
Dimensions: See Fig. 10 and 11.
Weight:
Small Body—5-1/4 lb (2.4 kg).
Large Body— 11-5/8 lb (5.3 kg).
Accessory: 201391 Shaft Adapter for 3/8 in. (10 mm) round
or square shaft (provided with both small body and large
body valves.
Approvals:
Underwriters Laboratories, Inc. (UL).
CSA.
EN161 Approval requires the use of an EN161-approved
actuator.
CE.
2
;
.

Advertisement

loading

This manual is also suitable for:

V5197a1003V5197a series