Lorentz PS200 Instructions For Installation Operation Service page 53

Solar water pump systems
Table of Contents

Advertisement

Electrical Testing Illustrated continued
Test 5
Speed indication of Pump.
By counting the ammount of flashes of the
Pump ON LED
the RPM of the pump can be read off
900 RPM Pump ON LED is ON
1200 RPM Pump ON LED flashes once
1600 RPM Pump ON LED flashes twice
2000 RPM 3 X flashing
2400 RPM 4 X flashing
2800 RPM 5 X flashing
Test 6A
Test 10
If a normally open (N.O.)
float switch is used, it is
wired this way.
To measure switch
circuit resistance,
DISCONNECT the wires
from terminals 3 & 4,
similar to Photo #7.
Test 6
Remove any one
pump wire and re-
make the connection
THROUGH your
meter. Probe
connections must be
secure. A clamping
device is helpful
Test 7
Analog (mechani-
cal) meter
requires zero-
adjustment. For
this test, you can
touch probes with
your fingers.
Test 11
If a normally closed (N.C.)
float switch OR pressure
switch is used, it is wired
this way.
To measure switch circuit
resistance, DISCONNECT
the wires from terminals 4 &
5, similar to Photo #7.
Other tests
See Section 9.2:
Check the low-
water probe and
check the full-tank
float switch
53