Warmhaus VIWA 90 Installation And User Manual

Warmhaus VIWA 90 Installation And User Manual

Wall mounted condensing boilers
Hide thumbs Also See for VIWA 90:

Advertisement

VIWA 90
VIWA 115
VIWA 125
VIWA 150
WALL MOUNTED CONDENSING BOILERS
INSTALLATION AND USER MANUAL

Advertisement

Table of Contents
loading

Summary of Contents for Warmhaus VIWA 90

  • Page 1 VIWA 90 VIWA 115 VIWA 125 VIWA 150 WALL MOUNTED CONDENSING BOILERS INSTALLATION AND USER MANUAL...
  • Page 2 Viwa 90 Viwa 115 Viwa 125 Viwa 150...
  • Page 3 CONDITIONS DEAR WARMHAUS 2.8. MOUNTING TO PARTIALLY- PROTECTED OUTER SPACES CUSTOMER 2.9. ELECTRIC CONNECTIONS 1.1. GENERAL WARNING 2.10. OPTIONAL CONTROLS: ROOM 1.2. GENERAL WARRANTY CONDITIONS THERMOSTAT, EXTERIOR 1.3. GAS LEAKS TEMPERATURE SENSOR AND OTHER 2.11. MOUNTING RULES FOR HYDRAULIC INSTALLATION PERSONNEL...
  • Page 4: Dear Warmhaus Customer

    For Warmhaus wall-mounted boilers; commissioning, adjustment, maintenance and cleaning must only be carried out by a specialist OR WARMHAUS declares that Viwa 90, Viwa 115, Viwa 125 & Viwa 150 approved service by Warmhaus! boilers comply with the essential requirements of the following...
  • Page 5: Gas Leaks

    WARMHAUS WARMHAUS 90 kW 115 kW 125 kW 150 kW 1015 18 1015 18 1015 18 1015 18 IMPORTANT INFORMATION It is a statutory requirement that all gas appliances are installed by competent persons, in accordance with the gas safety (installation and use) regulations (current edition).
  • Page 6 Gas categories for Warmhaus boilers are implemented on the CE certificate given below by SZU Test / BRNO;- appliance categories according to direct destinations are determined in accordance with EN 15502-1. According to-EN ISO 3166-1 destination countries;- millibar gas supply pressures, can be used for several gas groups if it is under normal pressure. They are specified with numerical values and "mbar"...
  • Page 7: Installation Personnel Section

    2.2. CONTENTS OF PACKAGE – Avoid twisting at the waist There are the following materials in the boiler box. In the Viwa 90-150 – Always grip with the palm of the hand boiler group, waste gas chimney sets are not supplied with the boiler –...
  • Page 8 G1 1/2" G 1" G 1" G1 1/2" G1 1/2" G1 1/2" Warmhaus Viwa 125 / Viwa 150 1) Heater Return Line 2) Sediment-Air Separator Discharge Line 3) Condensing Water Discharge Line 4) Gas Inlet Line 5) Heater Stream Line...
  • Page 9 Figure 2.8 Environmental locations of flue • It is recommended to mount the boiler between 1.8 - 2.2 m length Minimum Chimney Position of hanger plate from the ground. Distance • In places where mounting area is limited, the boiler must be Under a window 300 mm.
  • Page 10: Natural Gas Connection

    /h/kW) 2.4. NATURAL GAS CONNECTION (DEVICE VENTILATION “Viwa 90 - 150” boilers an be installed in boiler rooms whose size and CATEGORY I requirements meet current regulations. The following is provide for your Our boilers were manufactured to run with methane gas (G20).
  • Page 12: Filling The Siphon For Condensation Line

    If the Viwa 90, Viwa 115, Viwa 125 and Viwa 150 boilers are used as cascade systems and our blocking products are not used in each...
  • Page 13 Waste Gas Discharge with Concentric Exhaust Gas Discharge and Exhaust Gas Discharge Fresh Air Flue Connection Fresh Air Intake with Concentric Intake with Split Flue Sets Flue Sets and Split Flue Sets Caution: In case of using C33 type Split-Flue Set (for Caution: In use of C13 type chimney, a 90°...
  • Page 14 Ø100/150 mm chimneys to other elements of chimneys: condensate water drain to the boiler. a + b + c + d < 19 m = (Viwa 90) 19 m = (Viwa 115) connect the male (straight) side of concentric • The parts of standard horizontal flue...
  • Page 15 Ø100/150 mm Ø100/150 mm a + b + c + d + e + f < 19 m = (Viwa 90) Lmax= 18 m (Viwa 90) 19 m = (Viwa 115) Lmax= 17 m (Viwa 115) 18 m = (Viwa 125)
  • Page 16 Figure 2.27 Cascade Chimney Connection in the Attic with Concentric (Ø100/150mm) Chimney Sets Concentric (Optional) Chimney Accessories (Ø100/150 mm) for VIWA 90, 115, 125 and 150 Wall-Mounted Condensing Boilers Baca aksesuarları birbirlerine sıkı geçme ile yöntemi ile monte edilebilir ve bu nedenle bağlantı için ek bir paçaya gerek yoktur.
  • Page 17: Electric Connections

    Sizes and Weight: 128x99x36mm (compatible with box 503) 130g Power Supply: Bipolar and nonpolar cable WARMHAUS A.S. cannot be held responsible for any damage or loss that Power consumption: Max 18V (normal use), Max 23mA (max 250mW) may occur to a person or property due to the absence of grounding...
  • Page 18: Electrical Diagram

    Black Author Appr.; İsmail B.Taşdemir / R&D Mng. As this is the property of Warmhaus Isıtma ve Sogutma Sistemleri San. Tic. A.Ş. It Release date 16.7.2018 must not be passed on to any person not authorized by Warmhaus Isıtma ve Rev.
  • Page 19 EN 14336 with clean running water from the faucet. 2.11. MOUNTING RULES FOR HYDRAULIC For water treatment Warmhaus only permits the products listed below. INSTALLATION For the protection and long-term use of the heat exchanger, Warmhaus always specifies the following criteria for the quality of 2.11.1.
  • Page 20 Example: Antifrogen-N is toxic, Antifrogen-L is recommended) Viwa 90 boiler 90 kW, the total volume of the installation is 1100 litres. Note that all these products must be used strictly in accordance with The maximum permissible hardness for Viwa 90 can be obtained from the instructions of the water treatment manufacturers.
  • Page 21: Section 2 - Installation

    External Rainwater Downpipe (only combined foul/rainwater drain) Connection of Condensate Drainage Pipe to Internal Soil & Vent Stack Waterproof Open this valve and ensure that the pressure in Manometer reaches / Airtight up to 1-1.5 bar and close the Filling Valve by turning it clockwise and Combined waste Min Ø...
  • Page 22 3 m. Viwa 90 Wilo-YONOS PARA HF 25/7 pump set to be used under 152.11.003.000002 Viwa 115 Viwa 90 boiler, modulating pump, 2 unions, check valve and Viwa 125 gasket set. Dip the drainage pipe into the Pebble...
  • Page 24 High Temperature Programmable Room Thermostat High Temperature Programmable Room Thermostat Figure 2.42 Viwa 90, 115, 125 and 150 Boilers and Cascade System and 1 High Temperature (Radiator) and 1 Low Temperature (Local Heating) Zone Boiler and MLC30 Electrical Connection Diagram...
  • Page 25 RVS 43 boiler control device, Viwa 50-150 AVS 37 display module and RVS-AVS connection cable. Control unit for Viwa 90 - 150 Boilers that can cascade over OpenTerm for up to 8 boilers (up RVS 43.345 / 101 to 15-cascade) 153.11.660.600051...
  • Page 26 (with each other) 1 must be purchased if RVS unit is used for QAC34/101 Exterior 153.11.660.600071 Viwa 90 - 150 Boilers. The sensor that must be Viwa 90-150 Temperature Sensor connected to the RVS unit. Small screen room thermostat with Economy QAA55.110/101 Room Unit...
  • Page 27 In order for the Boiler not to be excluded from warranty coverage; its the heating installations by using Plated Heat Exchanger in a way remaining first operation must definitely be done by the Warmhaus Authorized no direct connection. Service. The following preliminary preparations must be made before •...
  • Page 28 ON-OFF Mode Pos No Operation Description By Pressing MODE button to select switch mode of the boiler. MODE order is OFF > SUMMER > WINTER > OFF as circle. Make sure that the " - - " is displayed on the screen to show device is OFF. If not press again the "MODE"...
  • Page 29: For Users

    Turn the boiler off during maintenance and repair work around the Our Authorized Service will give you information about how you will waste gas discharge chimneys. Make the Warmhaus Authorized use your boiler after checking and first-operating it. Service check the boiler before operating it after operations are finished.
  • Page 30     Figure 3.1 Control panel of Viwa 90-150 boilers SCREEN SYMBOLS Tanım: Viwa 90 - 115 - 125 - 150 POS NO Sembol Açıklama Kullanım Op. Mode Summer Symbol lit ( if boiler is in Summer mode) during Stand-by, Antifreeze, DHW.
  • Page 31 Digits used to display values for: - Delivery probe during heating stage, stand-by and all inertia discharges (post-circulation or post- ventilation, also at the end of a DHW stage). - DHW probe during DHW stage. - Flashing of heating/DHW set value during associated setting procedure. Main Digits - Flashing of value for parameter during associated setting procedure or reading.
  • Page 32 İsmail B.Taşdemir / R&D Mng. Appr.; As this is the property of Warmhaus Isıtma ve Sogutma Sistemleri San. Tic. A.Ş. It must not be passed on to any person not authorized by Warmhaus Isıtma ve Release date 17.05.2018 Sogutma Sistemleri San. Tic. A.Ş or be copied or otherwise utilized by anybody Rev.
  • Page 33 Operating in Winter Position 3.2.2. Resetting the Boiler (Restart) When the boiler is in this position, it operates both to heat the If the device is faulty/locked, you can reset the device by pressing the environment and to obtain hot domestic water (if a boiler is connected). RESET button and repeat the re-start process again.
  • Page 34 INFO 4: Display of Plant Probe temperature sensor OR AUX sensor temperature ( selectable by Par=52). Value is available ONLY / WHEN sensor connected. IF the sensor not available OR not connected the value shown as " - - " INFO 5: Display of fume temperature sensor.
  • Page 35 İsmail B.Taşdemir / R&D Mng. Appr.; As this is the property of Warmhaus Isıtma ve Sogutma Sistemleri San. Tic. A.Ş. It must not be passed on to any person not authorized by Warmhaus Isıtma ve Release date 17.05.2018 Sogutma Sistemleri San. Tic. A.Ş or be copied or otherwise utilized by anybody Rev.
  • Page 36 Mark (s) of conformity Burner control HDIMS50 granted BERTELLİ On all Viwa 90 - 150 kw boilers external sensor curve are given bellow; Symbol description; Calculation Agorithm; Şekil 3.3 Dış hava sıcaklık sensörü çalışma eğrileri Şekil 3.2 Exterior temperature sensor...
  • Page 37 3.3. FAULT FINDING & SOLUTIONS 3.3.1. Arıza Kodları Tablosu Fault Finding & Solutions Object: Viwa 90 - 115 - 125 - 150 This document has been composed to find possible faults and solve Attention: This procedure must be applied by authorised persons.
  • Page 38 ALL 10 Plant Probe Boiler does not work, ALL > Plant probe OR AUX 1-) Reset & Restart boiler 10 error code flashing on Probe temperature sensor 2-) Call for authorised service at first AUX Probe temperature the screen faulty sensor faulty >...
  • Page 39 ALL 70 Cascade Error Mater boiler Boiler does not work, ALL Fault ALL 70 displayed 1-) Call for authorised service at first 70 error code flashing on only on the master boiler 2-) Check slave boilers at first. the screen when an error is detected in 3-) Reset &...
  • Page 40: Warranty Conditions

    WARRANTY CONDITIONS Your boiler is set to ECO mode for economic use, we recommend not This warranty granted by WARMHAUS does not cover damages arising to change it. from abnormal use of product and the following conditions are out of...
  • Page 41: Teknik Veriler

    TEKNİK VERİLER Viwa 90 Viwa 155 Viwa 125 Viwa 150 Gas Circuit Birim Gas type Gas supply pressure mbar Gas Consumption at Maximum m³/h 9,301 11,55 12,737 15,27 Gas Consumption at Minimum m³/h 1,538 1,787 2,005 2,419 *(Natural Gas G20) Heat Load (Hu=10,56 kWh/m3)
  • Page 42 Warmhaus Viwa 50 & 150 boilers granted ErP & Product Fiche for Warmhaus boilers has been tested and reported on SZU Test / BRNO given below PRODUCT FICHE (according to EU regulation No 811/2013 and 814/2013 ) Viwa 50 Viwa 65...
  • Page 48 VIWA 90 VIWA 115 VIWA 125 VIWA 150...