11. REPLACEMENT OF SERVICE P.C. BOARD

11-1. Outdoor Unit

1. Setting the jumper wires and DIP switches
Part name
J800 to J803
Jumper wire
J804 to J810
SW802
DIP switch
SW803
SW804
Model switching (J800 to J803)
Since this service P.C. board is available for several models, cut the jumper wires according to the following table.
If they are not cut correctly, an error code "L10" or "L29" appears on the remote controller and the operation of
the air conditioner is disabled.
Model name
Factory setting (default)
RAV-SP1104AT
RAV-SP1404AT
∗ : Characters that indicate the following:
No character ... Standard models
J ...................... For heavily salt-affected areas
2. Installing the P.C. Board
(1) Apply thermal grease to the back (heat sink contacting side) of devices Q201, Q650, DB01, DB02 and
aluminum plate.( Q300 and Q400 are not necessary to be applied thermal grease.)
(2) Reuse the aluminum plate.
(3) Reuse the insulating sheet. When a small amount of thermal grease is applied to the back of the insulating
sheet, it adheres temporarily to the heat sink, which makes it easy to attach the insulating sheet.
(4) Insert the P.C. board, align the holes of the insulating sheets, semiconductor devices, and heat sinks, and
then secure them with screws.
(5) Connect the lead wires according to the wiring diagram stuck on the backside of the panel.
Apply thermal grease to the back
(heat sink contacting side) of
Q201,Q650, DB01, and DB02.
Function
Model switching
Settings
Settings
LED indication switching
Special operations for service
J 800
×
-E
-E
Reuse the insulating sheet.
Applying thermal grease to the back
of the insulating sheet makes it easy
to attach the insulating sheet.
Cut these jumper wires according to the following table.
Set these jumper wires to the settings of the P.C. board before
replacement.
Set SW802 to the setting of the P.C. board before replacement.
Set SW803 to all OFF.
Set SW804 to all OFF.
J 801
J 802
J 803
×
×
: Connected,
: Cut
Reuse the aluminum plate.
Apply thermal grease to
its both sides.
– 78 –
Setting
J800 to J803
SW804
J807~J810
J806
J805
J800~J804
Position of jumper wires
and DIP switches.
SW803
SW802