Setup At Local Site And Others; Calling Of Error History; Group Control Operation - Toshiba RAV-SP1404AT-E1 Service Manual

Air conditioner split type
Table of Contents

Advertisement

9-1. Calling of Error History

<Contents>
The error contents in the past can be called.
<Procedure>
1
SET
TEST
Push
+
buttons simultaneously for
4 seconds or more to call the service check mode.
Service Check goes on, the item code 01 is displayed, and
then the content of the latest alarm is displayed. The number
and error contents of the indoor unit in which an error oc-
curred are displayed.
2
In order to monitor another error history, push the set
temperature
history No. (Item code).
01 01 01 01 01
Item code
(Latest) → Item code
NOTE : 4 error histories are stored in memory.
3
Pushing
button returns the display to usual display.
TEST
REQUIREMENT
CL
Do not push
button, otherwise all the error histories of the
indoor unit are deleted.

9-2. Group Control Operation

In a group control, operation of maximum 8 indoor units can be controlled by a remote controller.
The indoor unit connected with outdoor unit (Individual/Master of twin) controls room temperature according to
setting on the remote controller.
<System example>
OUT
OUT
IN
IN
1-1
Remote controller
1. Display range on remote controller
The setup range (Operation mode/Air volume select/Setup temp) of the indoor unit which was set to the
master unit is reflected on the remote controller.
2. Address setup
Turn on power of the indoor unit to be controlled in a group within 3 minutes after setting of automatic
address.
If power of the indoor unit is not turned on within 3 minutes (completion of automatic address setting), the
system is rebooted and the automatic address setting will be judged again.
1) Connect 3 In/Out cables surely.
2) Check line address/indoor address/group address of the unit one by one.
3) The unit No. (line/indoor gout address) which have been set once keep the present status as a rule if the
unit No. is not duplicated with one of another unit.

9. SETUP AT LOCAL SITE AND OTHERS

/
buttons to change the error
04 04 04 04 04
(Old)
OUT
Master
IN
2-1
3-1
2
<Operation procedure>
OUT
IN
4-1
– 61 –
TEMP.
ON / OFF
TIMER SET
FAN
TIME
SAVE
FILTER
RESET
TEST
SET
CL
SWING/FIX
UNIT LOUVER
3 1
1
2
3
Returned to usual display
OUT
IN
7-1
Max. 8 units
MODE
VENT

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rav-sp1104at-e1Rav-sp1104atj-e1Rav-sp1404atj-e1

Table of Contents