Specifications; Technical Data - Siemens FDCL221 Technical Manual

Line separator
Hide thumbs Also See for FDCL221:
Table of Contents

Advertisement

8

Specifications

8.1

Technical data

Detector line
Line separator
External alarm indicators
Connections
Ambient conditions
Building Technologies
Fire Safety & Security Products
Operating voltage
Operating current (quiescent)
Maximum current connection factor
Quiescent current connection factor
Address connection factor
Separator connection factor
Protocol
Compatibility
Line voltage:
Nominal
Minimum
Maximum
Voltage at which the separator opens:
Minimum
Maximum
Permanent current when switches are
closed:
Switching current (e.g. in the event of
a short-circuit)
Leakage current when switches are
open:
Serial impedance when switches are
closed:
Number of external alarm indicators
that can be connected
Detector line:
Design
Cable cross section
Operating temperature/permissible
ambient temperature
Storage temperature
Air humidity
Protection categories according to
EN 60529 / IEC 60529
12 ... 33 V DC
250 µA
1
1
1
1
FDnet/C-NET
See 'List of compatibility'
32 V DC (= V
)
nom
12 V DC (= V
)
min
33 V DC (= V
)
max
7.5 V DC (= V
)
SO min
10.5 V DC (= V
)
SO max
Max. 0.5 A (= I
)
C max
Max. 1 A (= I
)
S max
Max. 1 mA (= I
)
L max
Max. 0.5 Ω (= Z
)
C max
None
Strands 500 mm long with pressed-on
2.8 x 0.8 mm flat connector sleeves
0.5 mm
2
-25 ... +70 °C
-30 ... +80 °C
≤95 % rel.
IP44
Specifications
27
007063_e_en_--
09.06.2009