ABB ACSM1 Firmware Manual page 244

Motion control program
Hide thumbs Also See for ACSM1:
Table of Contents

Advertisement

244
99.08 MOT NOM FREQ
Defines the nominal motor frequency.
Note: This parameter cannot be changed while the drive is running.
5...500 Hz
99.09 MOT NOM SPEED
Defines the nominal motor speed. Must be equal to the value on the motor rating plate. When
parameter value is changed, check the speed limits in parameter group
Note: This parameter cannot be changed while the drive is running.
0...30000 rpm
99.10 MOT NOM POWER
Defines the nominal motor power. Must be equal to the value on the motor rating plate. If several
motors are connected to the inverter, enter the total power of the motors. Set also parameter
MOT NOM
Note: This parameter cannot be changed while the drive is running.
0...10000 kW
99.11 MOT NOM COSFII
Defines the cosphi (not applicable to permanent magnet motors) for a more accurate motor model.
Not obligatory; if set, should be equal to the value on the motor rating plate.
Note: This parameter cannot be changed while the drive is running.
0...1
99.12 MOT NOM TORQUE
Defines the nominal motor shaft torque for a more accurate motor model. Not obligatory.
Note: This parameter cannot be changed while the drive is running.
0...2147483 Nm
Parameters and firmware blocks
FW block: None
Nominal motor frequency.
FW block: None
Nominal motor speed.
FW block: None
COSFII.
Nominal motor power.
FW block: None
Cosphi (0 = parameter disabled).
FW block: None
Nominal motor shaft torque.