ABB ACS480 Troubleshooting Manual page 18

General purpose drives, fault tracing
Hide thumbs Also See for ACS480:
Table of Contents

Advertisement

Code
Fault / Aux. code
(hex)
5091
Safe torque off
Programmable fault:
STO indication run/stop
5092
PU logic error
5093
Rating ID mismatch
5094
Measurement circuit
temperature
5089
SMT circuit
malfunction
5098
I/O communication
loss
50A0
Fan
5682
Power unit lost
5691
Measurement circuit
ADC
5692
PU board powerfail
5693
Measurement circuit
DFF
5696
PU state feedback
5697
Charging feedback
5698
Unknown PU fault
6181
FPGA version
incompatible
6306
FBA A mapping file
Cause
Safe torque off function is
active, ie. safety circuit
31.22
signal(s) connected to
connector STO is broken
during start or run.
Power unit memory has
cleared.
The hardware of the drive does
not match the information
stored in the memory. This
may occur e.g. after a firmware
update.
Problem with internal
temperature measurement of
the drive.
Safe motor temperature fault is
generated and STO
event/fault/warning is not
generated.
Note: If only one STO channel
is opened, fault
5090 STO
hardware failure
Communication failure to
standard I/O.
Cooling fan stuck or
disconnected.
Connection between the drive
control unit and the power unit
is lost.
Measurement circuit fault.
Power unit power supply
failure.
Measurement circuit fault.
State feedback from output
phases does not match control
signals.
Charging feedback signal
missing.
The power unit logic has
generated a fault which is not
known by the software.
Firmware and FPGA versions
are incompatible.
Fieldbus adapter A mapping
file read error.
What to do
Check safety circuit connections. For
more information, see chapter The Safe
torque off function in the Hardware
manual of the drive and description of
parameter
(page 244).
Check the value of parameter
Control board
Contact your local ABB representative.
Cycle the power to the drive. You may
have to be repeat this.
Contact your local ABB representative.
Check connection between the relay
output of the module and the STO
terminal.
is generated.
Try resetting the fault or cycle the power
to the drive.
Check fan operation and connection.
Replace fan if faulty.
Check the connection between the
control unit and the power unit.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Contact your local ABB representative.
Check the feedback signal coming from
the charging system
Check the logic and software
compatibility.
Reboot the control unit (using parameter
96.08 Control board
power. If the problem persists, contact
your local ABB representative
Contact your local ABB representative.
Fault tracing 17
31.22 STO indication run/stop
95.04
supply.
boot) or by cycling