ABB ACS480 Troubleshooting Manual page 16

General purpose drives, fault tracing
Hide thumbs Also See for ACS480:
Table of Contents

Advertisement

Code
Fault / Aux. code
(hex)
2381
IGBT overload
3130
Input phase loss
Programmable fault
3181
Wiring or earth fault
Programmable fault:
Wiring or earth fault
3210
DC link overvoltage
3220
DC link undervoltage
3381
Output phase loss
Programmable fault:
Motor phase loss
4110
Control board
temperature
4210
IGBT overtemperature Estimated drive IGBT
Cause
Excessive IGBT junction to
case temperature. This fault
protects the IGBT(s) and can
be activated by a short circuit
in the motor cable.
Intermediate circuit DC voltage
is oscillating due to missing
input power line phase or
blown fuse.
Incorrect input power and
motor cable connection (ie.
31.23
input power cable is connected
to drive motor connection).
Excessive intermediate circuit
DC voltage.
Intermediate circuit DC voltage
is not sufficient because of a
missing supply phase, blown
fuse or fault in the rectifier
bridge.
Motor circuit fault due to
missing motor connection (all
31.19
three phases are not
connected).
Control unit temperature is too
high.
temperature is excessive.
Fault tracing 15
What to do
Check motor cable.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive power.
Check input power line fuses.
Check for loose power cable
connections.
Check for input power supply imbalance.
Check input power connections.
Check that overvoltage control is on
(parameter
30.30 Overvoltage
Check that the supply voltage matches
the nominal input voltage of the drive.
Check the supply line for static or
transient overvoltage.
Check brake chopper and resistor (if
present).
Check deceleration time.
Use coast-to-stop function (if applicable).
Retrofit drive with brake chopper and
brake resistor.
Check that the brake resistor is
dimensioned properly and the resistance
is between acceptable range for the
drive.
Check supply cabling, fuses and
switchgear.
Connect motor cable.
Check proper cooling of the drive.
Check the auxiliary cooling fan.
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive power.
control).