9.3.2.3
1.
Make sure that the PSTX Softstarter is
disconnected from both operational voltage and
control supply voltage (100-250V).
2.
Connect the jumper cable to the Control Board
COM2 port, see section 3.1.5 Softstarter overview.
3.
Set the HMI in boot mode.
Hold both the Stop and L/R button when
connecting the USB cable between the PC and
the HMI, see Figure 9.16. All four LEDs (Ready,
Run, Protection and Fault) will light up. Release the
buttons and verify that all 4 LEDs are still lit.
4.
Remove the jumper cable.
INFORMATION
The Control Board need to restart itself into
application mode during the upgrade. If the
jumper cable is not removed this is not possible.
5.
Start the SoftstarterCare™ - Service Engineer Tool.
6.
An information dialog opens with the text "Your
PSTX Control Board is disconnected or is running
in boot mode". Click "OK".
7.
Click on "Firmware upgrade" on the tool bar of
the Service Engineer Tool to start the firmware
upgrade wizard.
8.
Select the firmware (.cab) files that where unzipped
during the preparation and then Click "Next".
9.
An information dialog opens with the text "Set HMI
in boot mode...". The PSTX Softstarter is already in
boot mode, Click "Next" to proceed.
10.
An information dialog opens with the text "Your
PSTX device is using an old Firmware...". Click
"Select" and set the PSTX model number manually.
Then Click "OK" to start the firmware upgrade.
11.
An information dialog opens with the text "Failed to
back up the parameters...". Click "Yes" to continue
with firmware upgrade.
INFORMATION
The firmware upgrade can take up to 15 minutes
to complete.
12.
An information dialog opens with the text "Failed
to backup and restore the parameters...". Click
"Finish" to exit the upgrade wizard.
13.
Restart the SoftstarterCare software.
14.
Restore all modified parameters by setting each
parameter to the value stored before the firmware
upgrade, see section 9.3.2.2 Backup parameters.
15.
Done.
L
N
100-250V
50/60 Hz
K4
Figure 9.16
Boot mode
1SFC132081M0201
| Installation and commissioning manual | Maintenance
Options
Options
K4
K4
Start Stop Reset In1 In2 DGND DND +24V GND
PSTX
4
3
Stop
2
Menu
Menu
1
1
4
4
Start
1
9
155