Upgrade firmware
9.3.1.2
1.
Make sure that the PSTX Softstarter is
disconnected from both operational voltage and
control supply voltage (100-250V).
2.
Set the HMI in boot mode.
Hold both the Stop and L/R button when
connecting the USB cable between the PC and
the HMI, see Figure 9.13. All four LEDs (Ready,
Run, Protection and Fault) will light up. Release the
buttons and verify that all 4 LEDs are still lit.
3.
Start the SoftstarterCare™ - Service Engineer Tool
and confirm that the PSTX Softstarter is connected
by checking the bottom status bar in Service
Engineer Tool.
4.
Click on "Firmware upgrade" on the tool bar of
the Service Engineer Tool to start the firmware
upgrade wizard.
5.
Select the firmware (.cab) files that where unzipped
during the preparation and then Click "Next".
6.
An information dialog opens with the text "Set HMI
in boot mode...". The PSTX Softstarter is already in
boot mode, Click "Next" to proceed.
7.
Click "Next" to use the default directory and start
the firmware upgrade.
INFORMATION
The firmware upgrade can take up to 15 minutes
to complete.
8.
An information dialog opens and ask whether to
restore parameters or not. Click "Yes" to restore
parameters.
9.
The upgrade is now completed. In order to
set parameters etc. in SoftstarterCare the
SoftastarterCare should first be restarted.
L
N
100-250V
50/60 Hz
K4
Figure 9.13
Boot mode
1SFC132081M0201
| Installation and commissioning manual | Maintenance
Options
Options
K4
K4
Start Stop Reset In1 In2 DGND DND +24V GND
PSTX
4
3
Stop
2
Menu
Menu
1
1
4
4
Start
1
9
153