ABB PSTX Series Installation And Commissioning Manual page 147

Hide thumbs Also See for PSTX Series:
Table of Contents

Advertisement

8.3
ABB Fieldbus plug interface
(option)
The PSTX Softstarter has an interface, com 2, on the
front for connecting the ABB Fieldbus Plug Adapter
(FBPA) used for Fieldbus communication.
You can use this interface to control the Softstarter, get
status information, and for the upload and download of
parameters.
The interface between the Softstarter and the FieldBus
Plug is independent of the Fieldbus protocol used.
Independent of Softstarter type or delivery date, you can
connect 1 of the available Fieldbus protocols, because
this is specified in the FieldBus Plug itself.
Connect the Fieldbus communication plug to the ABB
Fieldbus Plug Adapter (FBPA).
Make sure that the plug is in the correct position and
tighten the screw with 0,8 Nm (7,1 lb in) and additional
1/4 turn.
These Fieldbus protocols are available:
DeviceNet
Profibus (DPV0/DPV1)
Modbus RTU
8.3.1
Instructions
Instructions for the set-up of input and output telegrams,
parameter settings, instructions, etc. are available at:
www.abb.com/lowvoltage:
DeviceNet
1SFC132090M0201
Profibus (DPV0/DPV1) 1SFC132091M0201
Modbus RTU
1SFC132092M0201
8.3.2
Necesssary components
To connect the PSTX Softstarter to a Fieldbus system,
these components are necesssary:
ABB Fieldbus Plug Adapter, for presenting Fieldbus
protocol (make sure that the cable length is sufficient).
Connectors for bus connection.
End plug (some protocols).
Software for PLC set-up.
8.4
The PSTX Softstarter has an USB interface for
communication with PC. The USB interface is on the front
of the movable HMI.
You can use this interface to get status information, and
for the upload and download of parameters.
1SFC132081M0201
| Installation and commissioning manual | Communication
MINI USB interface
8
147

Hide quick links:

Advertisement

Table of Contents
loading