5.7.5 General specifications of fixed circuit-breakers
with rh lateral operating mechanisms for ABB UniSec switchgear (12 - 17.5 - 24 kV)
Circuit-breaker
Standards
Rated voltage
Rated insulation voltage
Withstand voltage at 50 Hz
Impulse withstand voltage
Rated frequency
Rated thermal current (40°C)
Rated duty breaking capacity
(symmetrical rated short-circuit current)
Short-time withstand current (3 s)
Making capacity
Sequence of operations
Opening time
Arcing time
Total break-time
Closing time
Overall dimensions
(maximum)
Weight
(1)
Absolute gas pressure (nominal duty value)
Application of PR521 protection device
Application of REF 601 protection device
Standardized dimensions table
Wiring diagram
Operating temperature
Tropicalization
Electromagnetic compatibility
(1)
increase the indicated weight by 20 kg for circuit-breakers with REF 601 devices and 3 current sensors (15 kg only with 2 current sensors)
the REF601 device and the current sensors are available on request. The rated current of the REF 601 must be set in the relay and must be compatible with the rated current of the
(2)
circuit-breaker. The rated current that can be set with CEI 0-16 is 80 A or 250 A. With the CEI 0-16 version of REF 601, the circuit-breaker is always supplied with 3 phase sensors
(Rogowsky coils) on the circuit-breaker itself, one 40/1 A closed-core toroidal TA and a -MU undervoltage release for relay-controlled opening
at 12 and 17.5 kV and at 630 A rated current, the rated short-time withstand current is 20 kA for 1 second
(3)
(4)
at 12, the rated short-time withstand current is 25 kA for 2 seconds
at 17.5 kV, the breaking capacity is 21 kA and the rated short-time withstand current is 21 kA for 3 seconds
(5)
16
[O - 0.3s - CO - 15s - CO]
H
D
L
Pole center-distance [mm]
with / without REF 601
IEC: 60068-2-30, 60721-2-1
HD4/R-SEC 12
IEC 62271-100
CEI EN 62271-100
(dossier 7642)
Ur [kV]
12
Us [kV]
12
Ud (1 min) [kV]
28
Up [kV]
75
fr [Hz]
50-60
Ir [A]
630
Isc [kA]
12.5
16
20
25
12.5
Ik [kA]
16
20
(3)
25
(4)
Ip [kA]
31.5
40
50
63
[ms]
45
[ms]
10...15
[ms]
55...60
[ms]
80
H [mm]
740
L [mm]
315
D [mm]
1049
230
[kg]
103
[kPa]
380
In [A]
1VCD003536
1VCD400119
[°C]
- 5 ... + 40
IEC 62271-1
HD4/R-SEC 17
17.5
17.5
38
95
50-60
800
630
800
12.5
12.5
16
16
16
20
20
20
(5)
(5)
25
12.5
12.5
16
16
16
20
20
20
(5)
(5)
25
(4)
31.5
31.5
40
40
40
50
50
50
63
45
10...15
55...60
80
740
315
1049
230
103
380
application not available
(2)
(2)
1VCD003536
1VCD400119
- 5 ... + 40
HD4/R-SEC 24
24
24
50
125
50-60
630
12.5
16
20
12.5
16
20
31.5
40
50
45
10...15
55...60
80
740
315
1049
230
103
380
(2)
1VCD003536
1VCD400119
- 5 ... + 40