ABB HD4/R Installation And Operating Instructions Manual page 13

Medium voltage products
Table of Contents

Advertisement

5.7.2 General specifications of fixed circuit-breakers
with rh lateral operating mechanisms for ABB UniSwitch switchgear (12 - 17.5 - 24 kV)
Circuit-breaker
Standards
Rated voltage
Rated insulation voltage
Withstand voltage at 50 Hz
Impulse withstand voltage
Rated frequency
Rated thermal current (40°C)
Rated duty breaking capacity
(symmetrical rated short-circuit current)
Short-time withstand current (3 s)
Making capacity
Sequence of operations
Opening time
Arcing time
Total break-time
Closing time
Overall dimensions
(maximum)
Weight
(3)
Absolute gas pressure (nominal duty value)
Application of PR521 protection device
Application of REF 601 protection device
Standardized dimensions table
Wiring diagram
Operating temperature
Tropicalization
Electromagnetic compatibility
increase the indicated weight by 20 kg for circuit-breakers with PR521 / PR512 / REF 601 devices and 3 current sensors (15 kg only with 2 current sensors)
((1)
rated current of the current sensors (the PR521 device and the current sensors are available on request)
(2)
the REF 601 device and the current sensors are available on request. The rated current of the REF 601 must be set in the relay and must be compatible with the rated current of the
(3)
circuit-breaker. The rated current that can be set with CEI 0-16 is 80 A or 250 A. With the CEI 0-16 version of REF 601, the circuit-breaker is always supplied with 3 phase sensors
(Rogowsky coils) on the circuit-breaker itself, one 40/1 A closed-core toroidal TA and a -MU undervoltage release for relay-controlled opening
special version with curves "ß = 1" or "ß = 1, RI" for the Belgian market: ask ABB for the availability, delivery lead times and wiring diagram
(4)
at 12 and 17.5 kV and at 630 A rated current, the rated short-time withstand current is 20 kA for 1 second
(5)
(6)
at 12 and with 25 kA breaking capacity, the rated short-time withstand current is 25 kA for 2 seconds
[O - 0.3s - CO - 15s - CO]
H
D
L
Pole center-distance [mm]
IEC: 60068-2-30, 60721-2-1
HD4/S 12
IEC 62271-100
CEI EN 62271-100
(dossier 7642)
Ur [kV]
12
Us [kV]
12
Ud (1 min) [kV]
28
Up [kV]
75
fr [Hz]
50-60
Ir [A]
630
800
Isc [kA] 12.5
12.5
16
16
20
20
25
25
Ik [kA] 12.5
12.5
16
16
20
20
(5)
25
25
(6)
Ip [kA] 31.5
31.5
40
40
50
50
63
63
[ms]
45
[ms]
10...15
[ms]
55...60
[ms]
80
H [mm]
710
L [mm]
286.5
D [mm]
1009
210
[kg]
90
[kPa]
380
In [A] 40 - 80 - 250 - 1250
see note
TN 7236
without protection
1VCD400018
device installed
with PR521
1VCD400018
with REF 601
1VCD400116
[°C]
- 5 ... + 40
IEC 62271-1
HD4/S 17
17.5
17.5
38
95
50-60
1250
630
800
1250
12.5
12.5
12.5
12.5
16
16
16
16
20
20
20
20
25
12.5
12.5
12.5
12.5
16
16
16
16
20
20
20
20
(5)
25
(6)
(6)
31.5
31.5
31.5
31.5
40
40
40
40
50
50
50
50
63
45
10...15
55...60
80
710
286.5
1009
210
90
380
40 - 80 - 250 - 1250
(2)
(3)
(3)
(4)
see note
(4)
TN 7236
1VCD400018
1VCD400018
1VCD400116
- 5 ... + 40
HD4/S 24
24
24
50
125
50-60
630
800
1250
12.5
12.5
12.5
16
16
16
20
20
20
12.5
12.5
12.5
16
16
16
20
20
20
31.5
31.5
31.5
40
40
40
50
50
50
45
10...15
55...60
80
710
286.5
1009
210
90
380
(2)
TN 7236
1VCD400018
- 5 ... + 40
13