Siemens OpenAir GLB141.1P Technical Instructions page 14

Electronic damper actuators, enhanced non-spring return rotary

Advertisement

Technical Instructions
Document Number 155-785
January 20, 2017
Start-Up/
Commissioning
Two-position/
Check Operation:
Floating
100 to 240 Vac
GLB34x
Check Auxiliary Switch A:
Check Auxiliary Switch B:
Page 14
OpenAir™ GLB Enhanced Non-Spring Return Rotary Electronic Damper Actuator
1.
Connect a Digital Multimeter (DMM) to the supply voltage wires.
2.
Verify that the supply voltage is between 100 and 240 Vac.
3.
Turn off the power supply.
1. Connect all wires per Figure 22.
2. Apply a control signal (100 to 240 Vac) to wires 4 (light blue) and 6 (black).
3. Allow the actuator shaft coupling to rotate from 0° to 90°.
4. Stop applying the control signal to wires 4 (light blue) and 6 (black).
5. Apply a control signal (100 to 240 Vac) to wires 4 (light blue) and 7 (white).
6. Allow the actuator shaft coupling to rotate from 90° to 0°.
1.
Set the DMM dial to ohms (resistance) or continuity check.
2.
Connect wires S1 and S3 to the DMM.
The DMM should indicate open circuit or no resistance.
3.
Apply a control signal (100 to 240 Vac) to wires 4 (light blue) and 6 (black). The DMM
should indicate contact closure as the actuator shaft coupling reaches the setting of
Switch A.
4.
Stop supplying the control signal to wires 4 (light blue) and 6 (black).
5.
Connect wires S1 and S2 to the DMM. The DMM should indicate open circuit or no
resistance.
6.
Apply a control signal (100 to 240 Vac) to wires 4 (light blue) and 7 (white). The DMM
should indicate contact closure as the actuator shaft coupling reaches the setting of
Switch A.
1.
Set the DMM dial to ohms (resistance) or continuity check.
2.
Connect wires S4 and S6 to the DMM. The DMM should indicate open circuit or no
resistance.
3.
Apply a control signal (100 to 240 Vac) to wires 4 (light blue) and 6 (black). The DMM
should indicate contact closure as the actuator shaft coupling reaches the setting of
Switch B.
4.
Stop applying the control signal to wires 4 (light blue) and 6 (black).
5.
Connect wires S4 and S5 to the DMM. The DMM should indicate open circuit or no
resistance.
6.
Apply a control signal (100 to 240 Vac) to wires 4 (light blue) and 7 (white) The DMM
should indicate contact closure as the actuator shaft coupling reaches the setting of
Switch B.