Configuration with TTH300 transmitters
Configuration parameters with effect on the safety function
All configuration parameters that are changed via HMI, DTM EDD or HART communication for
disabled write protection have an effect on the safety function of the device. The parameters are
described in the operating instructions. The safety function is checked according to the SIL
safety manual.
For redundancy mode with drift monitoring, the following parameters must be set in DTM, EDD:
Sensor type-Freestyle characteristics and Callendar van Dusen
Redundancy mode
14
When using these two configurations, it is necessary to check at least 3 reference points
to verify the configured characteristic. For complex curves, check several sampling points
according to complexity.
Pulse output
enabled
Pulse time
60 s, continuous pulse
Drift value
Configured acc. to customer application
Drift duration
max. 120 s.
SensyTemp TSP
SM/TSP/SIL-EN