Installation - Endress+Hauser Memograph M RSG40 Technical Information

Graphic data manager. record, visualize, analyze and communicate
Hide thumbs Also See for Memograph M RSG40:
Table of Contents

Advertisement

Memograph M
Orientation
Installation instructions
!
Endress+Hauser

Installation

Operating position as per DIN 16 257, NL 90 ± 30°
Panel cutout and installation / design, dimensions:
190
(7.48)
X
Y
All dimensions in mm or (inch)
• Installation depth without terminal cover: approx. 158 mm (6.22") (incl. terminals and fastening clips)
• Installation depth with terminal cover: approx. 197 mm (7,76")
+1
+1
• Panel cutout: 138
x 138
• Panel thickness: 2 to 40 mm (0.08 to 1.58")
• Max. viewing angle range: from the display central axis 50° in all directions
• Securing to DIN 43 834
Note!
• A distance of min. 7 mm (0.28 inch) between the devices has to be observed if aligning the devices in the
Y-direction (vertically above one another).
• The devices can be arranged horizontally beside one another in the X direction without any spacing between
the devices.
• The grid dimension of the panel cutouts for multiple devices must be min. 191 mm (7.52") horizontally and
min. 151 mm (5.94") vertically (tolerance not considered).
+0.04
+0.04
mm (5.43
x 5.43
")
5
141 (5.55)
(0.2)
157.8 (6.21)
192 (7.56)
191 (7.52)
53 (2.09)
138 (5.43)
23.3 (0.92)
35.1
(1.38)
11