Download Print this page

Weidmuller PMX420 Series Operating Instructions Manual page 12

4-digit current/voltage display

Advertisement

TerminalConnectionsforoutputcalibration
CalibrationStage
Analogue Current Output
Analogue Voltage Output
Procedure
Note: the procedure below shows calibration for the commonly used
-0 mA format. Expect different values for other formats.
Whenthe
Action/Description
displayshows
Put the instrument in setup mode and scroll through the main menu
COPn
Press ì or Å
COPy
Press ENT to select output calibration
I=
Connect the multimeter to measure the output current, then press ENT
Press ENT
Measure the output signal
4. 0 0
Adjust the output (using the ì or Å keys) until the output is at the value shown
When you are happy that the output is correct, press ENT
Press ENT
Measure the output signal
20. 0 0
Adjust the output (using the ì or Å keys) until the output is at the value shown
When you are happy that the output is correct, press ENT
Save
Continue with the setup sequence.
Note: Do not remove the power while the save message is on display.
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com
Signaltype
mA output +
mA output −
V output +
V output −
Terminal
21
22
21
22

Hide quick links:

Advertisement

loading

This manual is also suitable for: