This product is an IO-Link compliant product.
Connect this product by following the "
The controller can light, fl ash or extinguish the LEDs or control the buzzer.
Changing the "Operating Mode" settings enables the following modes:
 Simple Mode
 Advanced Mode
 Simple Mode
This mode performs simple control by only turning ON and OFF each LED and the buzzer.
Other settings are specifi ed using the parameters.
Send the processed data by referring to the table below.
bit 0
LED Unit (Red)
Byte 0 data
ON / OFF
LED Unit (Amber)
Byte 1 data
ON / OFF
LED Unit (Green)
Byte 2 data
ON / OFF
LED Unit (Blue)
Byte 3 data
ON / OFF
LED Unit (White)
Byte 4 data
ON / OFF
Buzzer
Byte 5 data
ON / OFF
 Advanced Mode
This mode performs advanced control such as lighting, fl ashing, and turning off each LED as well as sounding,
intermittently beeping, or stopping the buzzer.
Other settings are specifi ed using the parameters.
Send the processed data by referring to the table below.
Enable the intermittent buzzer settings to repeatedly sound the buzzer for 500 ms and stop the buzzer for 500 ms.
Refer to (p. 8) for the pattern of each LED.
bit 0
LED Unit (Red)
Byte 0 data
ON / OFF
LED Unit (Amber)
Byte 1 data
ON / OFF
LED Unit (Green)
Byte 2 data
ON / OFF
LED Unit (Blue)
Byte 3 data
ON / OFF
LED Unit (White)
Byte 4 data
ON / OFF
Buzzer
Byte 5 data
ON / OFF
5
Wiring" (p. 6).
bit 1
bit 2
Not used
Not used
bit 1
bit 2
Not used
Not used
Not used
Not used
Not used
Not used
– 7 –
bit 3
bit 4
Not used
Not used
bit 3
bit 4
LED pattern (Red)
LED pattern (Amber)
LED pattern (Green)
LED pattern (Blue)
LED pattern (White)
Intermittent
bit 5
bit 6
Not used
Not used
bit 5
bit 6
Not used
Buzzer
bit 7
Not used
bit 7
Not used
Not used
Not used
Not used
Not used