Precautions In Design; Precautions In Installation - AC&T System ETOS-XP Series User Manual

Industrial network server
Table of Contents

Advertisement

 Use the radio or mobile phone at least 30 cm away from the product. Otherwise, a
breakdown may occur.

[Precautions in Design]

 For control lines or communication cables, do not wire them together with main circuit or
power lines. Wiring must be done 100 mm or more away from them.
 When controlling the ETOS-XP series that is connected to a peripheral device, make sure that
the whole system operates safely at all times. In addition, be sure to read the manual
carefully and check safety before operating the ETOS-XP series. Especially, in the case of
controlling remote ETOS-XP series from an external device, it may not be possible to respond
immediately to troubles of ETOS-XP series due to data communication error. In the case of
data communication error, provide system-level countermeasures between external devices and
ETOS-XP series.

[Precautions in Installation]

Use the ETOS-XP Series in the environment of the general specifications described in this
manual. Otherwise, electric shock, fire, breakdown, damage to the product or burn may
occur.
Mount ETOS-XP series correctly when installing them. Failure to properly install the module
may cause breakdown, failure or dropping.
Be sure to shut off the power supply from the outside before installing or removing the
module (card). Failure to do so may result in electric shock or damage to the product.
Do not directly touch the conductive parts or electronic components of the module. It may
cause malfunction or breakdown of the device
If there is a lot of vibration in the installation environment, please do not allow the
vibration to directly affect the product. It may cause electric shock, fire or breakdown.
Do not allow metallic objects, water or liquid to enter into the product. It may cause
electric shock, fire or breakdown.
In dusty environments, use the product in an environment where dust has been blocked from
entering the product. It may cause fire or breakdown.
Install the product in a place with good ventilation.
Lightning, static electrical, etc. may cause damage to the product due to surge or noise.
If the communication cable is installed and wired outdoors, or installed and wired indoors,
where it is susceptible to surge or noise, SPD (Surge Protect Device) is recommended.
For power supply of ETOS-500XP, if one power supply module is used, it can be used as a
single power supply, and if two power supply modules are used, it can be used as a dual
power supply. Therefore, when used as a single power supply, mount the power supply module
on POWER1, and assuredly connect the power cable on the rear side to "POWER1".
Danger
Precaution
- 3 -