Power supply Specifications

2.2.
The following is the specifications for rated input voltage and power supply capacity for
each product.
Product
ETOS-100XP
ETOS-150XP
ETOS-500XP
2.3.

Battery Specification

The following is the standard for the battery information for each product. It is imperative
to read the precautions for battery use in the front of the manual before use.
The purpose of the battery is to save the log area and user memory data and to operate RTC.
It is not possible to charge the pertinent battery, therefore, it is imperative to replace it
in case of discharge.
** For purchasing a battery, contact our sales department.

2.3.1. Battery Application Status and Parts by Product

Application
Product
Status
ETOS-100XP
ETOS-150XP
ETOS-500XP

2.3.2. Precautions for Use

(1) Do not charge, disassemble, heat, put into fire, short circuit, solder or give a shock to
the battery.
(2) Handling battery incorrectly may cause injury to the human body due to heat, breakage and
so on. There is a risk of fire.
2.3.3. Battery Life
(1) It is possible to use the battery for at least 2 years by using it at room temperature
(based on 25 degree), but battery life depends on the power failure time and temperature
conditions.
(2) If the battery voltage drops below 1.5V, the system flag (SysBatteryLow) and log information
of the ETOS-RD can be used to check the battery voltage drop warning.
(3) If a warning for low battery voltage occurs, replace the battery as soon as possible for
operation.
(4) If the battery voltage becomes low, regular check and replacement management is required
because it can affect log data storage, user memory data storage, and RTC operation.
** When replacing the battery, it is recommended to replace the battery within 2 hours because
the internal supercap backup is possible only up to 2 hours.
** Before replacing the battery, please perform user memory and log backup.
** After purchasing, a warning occurs generally after about two years. But if the battery is
Input Power Supply
AC 100V ~ 240V Free Voltage
(50/60Hz)
90 ~ 130 VDC
Battery
Specification
Name
O
XL-050F
Lithium
O
XL-050F
Lithium
O
XL-050F
Lithium
- 13 -
Current
Power
Consumption
Consumption
300mA or less
300mA or less
600mA or less
128VA
Nominal
Size (mm)
voltage /
(height x diameter)
current
3.6V/1.2A
28 x 16.6
3.6V/1.2A
28 x 16.6
3.6V/1.2A
28 x 16.6
64VA
64VA
130W