Control Wire Tap - Siemens Sentron 3VA Manual

Protection devices molded case circuit breakers with ul and iec certification
Hide thumbs Also See for Sentron 3VA:
Table of Contents

Advertisement

4.3.4.2

Control wire tap

The portfolio of the 3VA UL molded case circuit breaker enables easy implementation of a
control wire tap.
Note
A maximum current limit of 15 A applies to all control wire taps for 3VA UL molded case
circuit breakers. Control wire overcurrent protection must be applied separately.
The control wire tap must be taken into account when configuring the molded case circuit
breaker. Suitable cable cross-sections: Cables up to maximum AWG 14 / 2.5 mm
connected.
3VA molded case circuit breakers with UL and IEC certification
Manual, 01/2019, L1V30435333-01
Accessories
4.3 Connection system