Protection devices molded case circuit breakers with ul and iec certification
Hide thumbs Also See for Sentron 3VA:
Table of Contents

Advertisement

Applications
3.1 Use of the 3VA UL molded case circuit breakers in line protection
Overload protection L:
The ETU350 LSI has a permanently active thermal memory.
Short-time delayed short circuit protection S:
The curve shape is I
Instantaneous short-circuit protection I:
Neutral conductor protection N:
The neutral conductor protection function is available for 4-pole molded case circuit breakers
only.
116
I
Adjustable in 10 steps from 0.4 to 1.0 x I
r
0.4 / 0.5 / 0.6 / 0.7 / 0.75 / 0.8 / 0.85 / 0.9 / 0.95 / 1.0
t
Adjustable in 10 steps from 0.5 to 12 /15 s or 17 s:
ld
t
is the tripping time with 6 x I
ld
I
Adjustable in 10 steps from 1.5 to 9 / 10 x I
sd
t
Adjustable in 6 steps from 0 to 0.4 s
sd
with the reference point at I
t = constant.
2
I
Not adjustable: Permanently set to 9 / 10 / 11 / 12 x I
i
(depending on rated operational current and breaker frame size)
I
I
< 100 A: 1.0 x I
N
n
I
≥ 100 A: 0.5 / 1.0 x I
n
r
= 8 x I
sd
r
or OFF
r
or OFF
r
3VA molded case circuit breakers with UL and IEC certification
:
n
r:
n
Manual, 01/2019, L1V30435333-01