Protection devices molded case circuit breakers with ul and iec certification
Hide thumbs Also See for Sentron 3VA:
Table of Contents

Advertisement

Short-time delayed short circuit protection S:
The curve shape I
Instantaneous short-circuit protection I:
Ground-fault alarm (G):
The detection of the ground-fault current is based on a vectorial summation of the phase
currents and the neutral conductor current for 4-pole or 3-pole circuit breakers with external
current transformer for N conductor.
An alarm threshold I
The current-dependent curve shape I
If a ground fault is detected, the ETU556 or ETU856 only issues an alarm without tripping
the circuit breaker. This alarm is displayed directly on the LCD display and/or communicated
to higher-level systems via the communication connection, the EFB external function box
and the maintenance mode box.
Neutral conductor protection N:
The neutral conductor protection function is available only for 3-pole molded case circuit
breakers with external current transformer for N conductor for 4-pole molded case circuit
breakers.
3VA molded case circuit breakers with UL and IEC certification
Manual, 01/2019, L1V30435333-01
3.1 Use of the 3VA UL molded case circuit breakers in line protection
I
Adjustable from 0.6 to 9 / 10 x I
sd
I
= 40 A: In steps of 0.5 A
sd
I
≥ 100 A: In steps of 1 A
sd
t
Adjustable from 0.05 to 0.5 s
sd
with a reference point of I
in steps of 0.01 s
t = constant can be deactivated.
2
I
Adjustable from 1.5 to 9 / 10 / 12 x I
i
and frame size)
In steps of 1 A
I
Adjustable from 0.2 / 0.4 to 1.0 x I
g
In steps of 1 A
t
Adjustable from 0.05 to 0.8 s
g
with a reference point of 2 x I
In steps of 0.01 s
from 0.2 / 0.4 to 1 x I
gA
I
Adjustable in steps of 1 A
N
3-pole circuit breakers with external current transformer for N conductor:
I
= 40 A: 0.4 to 1.6 x I
n
I
≥ 100 A: 0.2 to 1.6 I
n
4-pole circuit breakers:
I
= 40 A: 0.4 to 1.6 x I
n
I
≥ 100 A: 0.2 to 1.0 or 1.5 / 1.6 x I
n
n
= 8 x I
sd
r
(dependent on rated operational current
n
in absolute current values
n
g
can also be set. In steps of 1 A
n
t = constant can be deactivated.
2
n
n
n
n
Applications